Seitenansicht 51
If there is no electronics module available on site, one can
be ordered
from the VEGA agency serving you.
The new electronics module must be loaded with the settings of the
sensor. These are the options:
l At the factory by VEGA
l Or on site by the user
In both cases, the sensor serial number is needed. The serial numbers
are stated on the type label of the instrument, inside the housing or on
the delivery note.
Information:
When loadin
g on site, rst of all the order data must be downloaded
from the Internet (see operating instructions manual "Oscillator").
The electronics modules are adapted to the respective sensor and
distinguish also in the signal output or power supply.
8.4 Software update
The software version of VEGAPULS 61 can be determined as follows:
l on the type label of the electronics
l via the indicating and adjustment module
l via PACTware
You can view all software histories on our website
www.vega.com.
Make u
se of this advantage a nd get registered for update information
via e-mail.
The following components are required to update the sensor software:
l Sensor
l Voltage supply
l VEGACONNECT
l PC with PACTware
l Current sensor software as le
At "
www.vega.com/downloads" go
to "Software". Select under "plics
instruments and sensors" the suitable instrument series. Load the zip
le via the right mouse key with "Save target as" e.g. on the desktop of
your PC. Extract all les available in the zip le, e.g. to the desktop.
Connect the sensor to power supply and provide connection from PC
to the instrument via VEGACONNECT. Start PACTware and provide
connection to the sensor, e.g. via the VEGA project assistant. Close
the parameter window of the sensor, as far as open.
Go in the PACTware menu bar to "Instrument data", "Additional
functions" and "Update instrument software".
PACTware now checks the actual hardware and software version of
the sensor and displays the data. This procedure lasts approx. 60 s.
Sensor serial number
Assignment
Load sensor software to
PC
Prepare update
Load software into sen-
sor