8 Diagnosis, Asset Management and service
VEGAPULS 62 • Modbus and Levelmaster protocol
41362-EN-121011
8.4 Measurementerrorduringlling
Fault description Error pattern Cause Rectication
4. Measured value re-
mains unchanged
during lling
Level
time
0
False echoes in the close range
too big or product echo too
small
Strong foam or spout genera-
tion
Max. adjustment not correct
Eliminate false echoes in the
close range
Check measurement situation:
Antenna must protrude out of
the socket, installations
Remove contamination on the
antenna
Minimize interfering instal-
lations in the close range by
changing the polarization
direction
Create a new false signal sup-
pression
Adapt max. adjustment
5. Measured value re-
mains in the bottom
section during lling
Level
time
0
Echo from the tank bottom
larger than the product echo,
for example, with products with
ε
r
< 2.5 oil-based, solvents
Check application parameters
Medium, Vessel height and
Floor form, adapt if necessary
6. Measured value re-
mains momentarily
unchanged during ll-
ing and then jumps to
the correct level
Level
time
0
Turbulence on the product
surface, quick lling
Check application parameters,
change if necessary, e.g. in
dosing vessel, reactor
7. Measured value
jumps towards 0 %
during lling
Level
time
0
Amplitude of a multiple echo
(vessel top - product surface) is
larger than the level echo
Check parameter "Application",
especially vessel top, product
type, dished end, high dielectric
gure, adapt if necessary
The level echo cannot be distin-
guished from the false echo at
a false echo position (jumps to
multiple echo)
Remove/reduce false echo:
minimize interfering installa-
tions by changing the polariza-
tion direction
Chose a more suitable installa-
tion position
8. Measured value
jumps towards 100 %
during lling
Level
time
0
Due to strong turbulence and
foam generation during lling,
the amplitude of the product
echo sinks. Measured value
jumps to the false echo
Carry out false signal suppres-
sion
9. Measured value
jumps sporadically to
100 % during lling
Level
time
0
Varying condensation or con-
tamination on the antenna
Carry out a false signal sup-
pression or increase false
signal suppression with con-
densation/contamination in the
close range by editing
10. Measured value
jumps to ≥ 100 % or
0 m distance
Level
time
0
Level echo is no longer
detected in the close range
due to foam generation or false
echoes in the close range. The
sensor goes into overll protec-
tion mode. The max. level (0 m
distance) as well as the status
message "Overll protection"
are outputted.
Check measuring site: Antenna
must protrude out of the socket
Remove contamination on the
antenna
Use a sensor with a more suit-
able antenna