Operating InstructionsRadar sensor for continuous level measurement of liquidsVEGAPULS 62 standpipe ver-sion4 … 20 mA/HART - two-wireDocument ID: 3650
103 Product descriptionVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210113 Product description3.1 CongurationThe type label c
113 Product descriptionVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011The instrument is available in two dierent electronics
123 Product descriptionVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210113.3 Packaging, transport and storageYour instrument wa
133 Product descriptionVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011It is suitable for measured value indication and adjust
144 MountingVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210114 Mounting4.1 General instructionsWith instruments with threaded
155 Connecting to power supplyVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210115 Connecting to power supply5.1 Preparing the
165 Connecting to power supplyVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Warning:Signicant potential dierences exist in
175 Connecting to power supplyVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Fig. 3: Connection steps 5 and 66. Insert the w
185 Connecting to power supplyVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210115.3 Wiring plan, single chamber housing512+( )
195 Connecting to power supplyVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210114...20mA2312+( )(-)1Fig. 6: Connection compartm
2Quick startVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Quick startThe quick start enables a quick setup with many applica
205 Connecting to power supplyVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210114...20mA212+( )(-)1Fig. 9: Connection compartme
215 Connecting to power supplyVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011• Indication of the instrument type, hardware an
226 Set up with the indicating and adjustment moduleVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210116 Set up with the indicat
236 Set up with the indicating and adjustment moduleVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210111 2Fig. 13: Insertion of t
246 Set up with the indicating and adjustment moduleVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011 – Edit parameter – Save v
256 Set up with the indicating and adjustment moduleVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011You can nd in the operati
266 Set up with the indicating and adjustment moduleVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011100%0%0,5 m(19.68")5
276 Set up with the indicating and adjustment moduleVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210114. Enter the suitable dis
286 Set up with the indicating and adjustment moduleVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011The "Echo curve"
296 Set up with the indicating and adjustment moduleVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011The following circumstance
3Quick startVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011The quick start is then nished. For further information see chapt
306 Set up with the indicating and adjustment moduleVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011If a false signal suppress
316 Set up with the indicating and adjustment moduleVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011With radar sensors with st
326 Set up with the indicating and adjustment moduleVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Menu Menu item Default val
337 Setup with PACTwareVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210117 Setup with PACTware7.1 Connect the PC312Fig. 16: Co
347 Setup with PACTwareVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011such cases, the interface converter can be connected pa
357 Setup with PACTwareVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011and echo curves. In addition, there is a tank calculati
368 Set up with other systemsVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210118 Set up with other systems8.1 DD adjustment pr
379 Diagnosis, Asset Management and serviceVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210119 Diagnosis, Asset Management and
389 Diagnosis, Asset Management and serviceVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Further echo curves: Up to 10 echo
399 Diagnosis, Asset Management and serviceVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011The following table shows the error
4ContentsVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Contents1 About this document1.1 Function ...
409 Diagnosis, Asset Management and serviceVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011CodeText mes-sageCause Rectication
419 Diagnosis, Asset Management and serviceVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011CodeText mes-sageCause Rectication
429 Diagnosis, Asset Management and serviceVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Error Cause Rectication4 … 20 mA s
439 Diagnosis, Asset Management and serviceVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210119.4 Measurement error with constan
449 Diagnosis, Asset Management and serviceVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Fault description Error pattern Cau
459 Diagnosis, Asset Management and serviceVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011You can nd the actual sensor softw
4610 DismountingVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-12101110 Dismounting10.1 Dismounting stepsWarning:Before dismountin
4711 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-12101111 Supplement11.1 Technical dataGeneral data316L corresponds t
4811 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210113421Fig. 27: Data of the input variable1 Reference plane2 Mea
4911 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Accuracy (according to DIN EN 60770-1)Process reference conditi
5ContentsVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210119.3 Asset Management function ...
5011 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Gas phase Temperature Pressure1 bar (14.5 psig)10 bar (145 psig
5111 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Seal Antenna impedance coneProcess temperature (measured on the
5211 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Indicating and adjustment moduleVoltage supply and data transmi
5311 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011120092750075025012 18169,614 2015,12224262830323436Ω V 14 23 Fi
5411 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Plastic housing~ 69 mm(2.72")ø 79 mm(3.03")112 mm (4.
5511 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Aluminium housing in protection rating IP 66/IP 68, 1 bar120 mm
5611 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011Stainless steel housing in protection rating IP 66/IP 68, 1 bar
5711 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011VEGAPULS 62, standpipe version with threadø 21,3 mm(0.84")
5811 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011VEGAPULS62,standpipeversionwithangeø 39,5 mm(1.56")ø
5911 SupplementVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-12101111.3 Industrial property rightsVEGA product lines are global p
61 About this documentVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210111 About this document1.1 FunctionThis operating instruc
60INDEXVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011INDEXAAccessories – External indicating and adjustment unit 12, 13 – E
61INDEXVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011VVoltage supply 15
62NotesVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011
63NotesVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-121011
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36507-EN-121011All statements concerning scope of delivery, application, practi
72 For your safetyVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210112 For your safety2.1 Authorised personnelAll operations de
82 For your safetyVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210112.5 CE conformityThe device fullls the legal requirements
92 For your safetyVEGAPULS 62 standpipe version • 4 … 20 mA/HART - two-wire36507-EN-1210112.9 Environmental instructionsProtection of the environment