4 Capacitive electrodes EK with signal conditioning instrument
Product description
1 Product description
1.1 Function and configuration
Capacitive electrodes series EK detect levels
of virtually any medium, unaffected whether
liquids, powders, granules or pastes. This is
also valid for adhesive mediums.
The electrode measures also the level ca-
pacitance and the ohmic resistance (admit-
tance processing). Hence also problematic
mediums and solids with fluctuating humidity
contents can be detected.
By the use of screening tubes and screen
segments, inactive areas can be provided on
the probe where pollution, condensation or
permanent build-up do not influence the
measuring result.
Measuring principle
Electrode, medium and vessel wall form an
electrical capacitor.
The capacitance of the capacitor is mainly
influenced by three factors:
- distance of the electrode plates (a)
- size of the electrode plates (b)
- kind of dielectricum between the electro-
des (c)
b
c
Fig. 1.1 Plate capacitor (schematic demon-
stration)
Electrode and vessel wall are the capacitor
plates. The medium is the dielectricum. Due
to the higher dielectric constant figure (DK-
value) of the medium against air, the capaci-
tance of the capacitor increases with raising
covering of the electrode.
Fig. 1.2 Capacitance change with covered
electrode
The capacitance change is converted by the
oscillator into a level proportional, floating
current in the range of 4 20 mA or into a
switching command.
Continuous level measurement
With the continuous level measurement, the
appropriate level is continuously detected
and converted into a level proportional signal
which is either directly indicated or further
processed.
You require a capacitive electrode series EK
with oscillator and a signal conditioning in-
strument VEGAMET, converting the propor-
tional current of the oscillator into
standardised current and voltage signals.
The continuous measurement requires a
constant dielectric constant figure e
r
, i.e. if
possible the medium should have steady
features.