36 Pressure transmitter D84
Click to "
Offset correctionOffset correction
Offset correctionOffset correction
Offset correction
".
When the sensor is unpressurised and in
installation position, confirm the safety
enquiry with "
OKOK
OKOK
OK
".
You see the actual measured value from the
sensor.
Click to "
CorrectCorrect
CorrectCorrect
Correct
".
Setup
The example shows an absolute pressure
transmitter with a measuring range of
0 1000 mbar, with which low pressures
(partial vacuum) are measured. The min.
value was set to 50 mbar and the max. value
(span) to 1000 mbar (i.e. the final value of the
measuring range).
Confirm your adjustments with "
OKOK
OKOK
OK
" and
after a short data transmission to the
sensor, you are again in the menu window
"
Adjustment
".
Quit all menu windows with "
QuitQuit
QuitQuit
Quit
" and you
are again in the initial menu.
Offset correction (not possible with abso-
lute pressure transmitters)
With this menu you can carry out a zero point
correction/position correction (unpressurized
sensor).
Choose in the initial menu "
Instrument data/
Parameter adjustment
" the item "
AdditionalAdditional
AdditionalAdditional
Additional
functionsfunctions
functionsfunctions
functions
".