Vega D86_D87 Hydrostatic pressure transmitters Bedienungsanleitung Seite 16

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 40
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 15
16 Pressure transmitters D86/D87
Mounting
2 Mounting
2.1 Mounting instructions
The pressure transmitter can be mounted in
any position. Cable entries must point down-
wards to avoid moisture ingress. For this
purpose, the housing can be rotated by 330°
in relation to the mounting part.
An appropriate connection seal must be
used for mounting. This seal is either sup-
plied with the pressure transmitter or must be
provided by the customer.
2.2 Compensation of the atmos-
pheric pressure
On instruments for gauge pressure meas-
urement, the atmospheric pressure is com-
pensated via a breather facility integrated in
the housing.
Pressure transmitter with direct cable
outlet
- via the capillaries of a special cable con-
nected to the terminals, protection IP 68
We recommend leading the special cable into
the external connection housing VEGABOX
01 (accessory) and carrying out the pres-
sure compensation via the integrated
breather facility there.
External connection housing
Observe the following instructions:
- as a rule, there must be the same atmos-
pheric pressure on the breather facility as
on the vessel
- the pressure compensation must be done
in a dry environment
- with vertical wall mounting, cable entries
must point downward to avoid moisture
ingress and buildup on the breather facility.
Pressure transmitter with housing
- via an integrated breather facility (PTFE
use
1)
), protection IP 66
- via the capillaries of a special cable con-
nected to the terminals, protection IP 67
1)
air permeable and humidity blocking
Seitenansicht 15
1 2 ... 11 12 13 14 15 16 17 18 19 20 21 ... 39 40

Kommentare zu diesen Handbüchern

Keine Kommentare