13
4 Mounting
POINTRAC 31 • Foundation Fieldbus
41779-EN-131119
4.2 Mounting instructions
Note:
Along with the planning, our specialists will analyse the conditions of
the measurement loop to dimension the radiation source (isotope)
accordingly.
Yougeta"SourceSizing"documentspecifyingtherequiredsource
activity and containing all relevant mounting information for your
measuring point.
Youmustfollowtheinstructionsofthis"SourceSizing"documentin
addition to the following mounting instructions.
The following mounting information is applicable as long as there is
nothingelsespeciedinthe"SourceSizing"document.
2
1
Fig. 3: Mounting position - level detection
1 Vertical mounting
2 Mounting horizontally, at right angles to container
Youcanndinformationonprotectivebarriersandthemounting
of the corresponding source container in the operating instructions
manualofthesourcecontainer,e.g.VEGASOURCE.
Forleveldetection,thesensorisgenerallymountedhorizontallyatthe
height of the requested limit level. Make sure that there are no struts
or reinforcements at this position in the vessel.
Direct the exit beam of the source container exactly towards the
measuring range of POINTRAC 31.
Fasten the sensor in such a way that it cannot fall out of the holder. If
necessary, provide the sensor with a support from below.
Mount the source container and POINTRAC 31 as close as possible
to the vessel. If there are gaps, secure the area with a safety fence
Installation position