Setup
Note:
After adjustment of a parameter, push "ENTER“ and then "SEND“.
Confirm the message to switch over to manual operation with "OK“.
Confirm the message to reset to automatic operation also with "OK“.
Only then will the adjustment be stored in the sensor and take effect.
1.2.3.1.1
Generic: SENSOR
Current applied
process value :10.945 mbar
1 Set as 4 mA value
2 Read new value
3 Leave as found
ABORT ENTER
1.2.3.1.2
Generic: SENSOR
Current applied
process value:
85.281 mbar
1 Set as 20 mA value
2 Read new value
3 Leave as found
ABORTENTER
Generic: SENSOR
Choose analog output
level
14 mA
2 20 mA
3 Other
4End
ABORT ENTER
Generic: SENSOR
WARN-Loop should be
removed from
automatic control
ABORT OK
Generic: SENSOR
Ser the:
14 mA
2 20 mA
3Exit
ABORT ENTER
Generic: SENSOR
Apply new 20 ma input
ABORT OK
Generic: SENSOR
Current applied
process value:
85.281 mbar
1 Set as 20 mA value
2 Read new value
3 Leave as found
ABORT ENTER
Generic: SENSOR
Set the :
14 mA
2 20 mA
3Exit
ABORT ENTER
Generic: SENSOR
Apply new 4 ma input
ABORT OK
Generic: SENSOR
Current applied
process value:
10.945mbar
1 Set as 4 mA value
2 Read new value
3 Leave as found
ABORT ENTER
Menu windows are displayed but not
supported by the sensor.
Saving of adjustments carried out here is
therefore not possible.
1.4.3.1.3
1.4.3.1.2
Generic: SENSOR
AO Alrm typ
Lo
EXIT
Low: In case of failure, current output
goes to 22 mA
High: In case of failure, current output
goes to < 3.6 mA
1.4.3.2
Generic: SENSOR
HART output
1 Poll addr
2 Num req preams 0
3 Burst mode Off
4 Burst option
HELP SAVE HOME
1.4.3.1
Generic: SENSOR
Analog output
1 AO1 13.467mA
2 AO Alrm typ Lo
3 Loop test
4 D/A trim
5 Scaled D/A trim
HELP SAVE HOME
}
Off
On
Not used
Non
Unused
Special
Generic: SENSOR
Fld dev output is
fixed at 4.000 mA
ABORT O K
Sensor signals measured values only on
request
Sensor signals measured values
unrequested
Choice is not supported
1.4.3.2.3
Generic: SENSOR
Burst mode
Off
On
Not used
None
Unknown
ESC ENTER
1.4.3.2.4
Generic: SENSOR
Burst option
*************
PV
% range/current
Process vars/crnt
HELP ESC ENTER
Leave the Burst-mode in
OFF-position
Choice is not supported
1.2.3.1.1.1
1.2.3.1.2.1
1.4.3.1.3
1.4.3.1.3.1