10 Supplement
VEGABAR 52 • Foundation Fieldbus - climate compensated
36789-EN-130321
Highest calibrated value. For calibration of the high limit point you give the high measurement
value(pressure)tothesensorandtransferthispointasHIGHtothetransmitter.Unitderives
from 'Sensor_range.unit'
CAL_POINT_LO
Lowest calibrated value. For calibration of the low limit point you give the low measurement
value(pressure)tothesensorandtransferthispointasLOWtothetransmitter.Unitderives
from 'Sensor_range.unit'
CAL_MIN_SPAN
Minimum calibration span value allowed. Necessary to ensure that when calibration is done,
thetwocalibratedpoints(highandlow)arenottooclosetogether.Unitderivesfrom'Sen-
sor_range.unit'
SCALE_IN
Min/max-adjustment:Upperandlowercalibratedpointsofthesensor.Unitderivesfrom'Sen-
sor_range.unit'
trimmed_value
Sensorvalueafterthetrimprocessing.Unitderivesfrom'Sensor_range.unit'
sensor_sn
Sensor serial number
temperature
Processtemperature.SelectedasinputtoAIFBbysetting'Channel'=4.Unitderivesfrom
'Temperature.unit'
temperature_unit
Unitcodeof'Temperature','Max/Min_peak_temperature_value'
°C, °F, K, °R
max_peak_temperature_value
Holdsthemaximumprocesstemperature.Writeaccessresetstocurrentvalue.Unitderives
from 'Temperature.unit'
Write access resets to current value
min_peak_temperature_value
Holdstheminimumprocesstemperature.Writeaccessresetstocurrentvalue.Unitderives
from 'Temperature.unit'
Write access resets to current value
10.3 Dimensions
The following dimensional drawings represent only an extract of the possible versions. Detailed
dimensional drawings can be downloaded on www.vega.comunder"Downloads"and"Drawings".
The double chamber housings are only available for Ex-d version with instruments with 4 … 20 mA
signal output.