Vega VEGABAR 53 4 … 20 mA_HART Bedienungsanleitung Seite 45

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 68
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 44
45
8Maintenanceandfaultrectication
VEGABAR 53 • 4 … 20 mA/HART
36722-EN-130321
Error code Cause Rectication
4 … 20 mA
signal not
stable
Leveluctuations Set the integration time via the
display and adjustment module or
PACTware
No atmospheric pres-
sure compensation
Check the pressure compensation
inthehousingandcleanthelter
element, if necessary
4 … 20 mA
signal miss-
ing
Connection to volt-
age supply wrong
Check connection according to
chapter"Connection steps"and
if necessary, correct according to
chapter"Wiring plan"
No power supply
Checkcablesforbreaks;repairif
necessary
Operating voltage
too low or load resist-
ance too high
Check, adapt if necessary
Current sig-
nal greater
than 22 mA
or less than
3.6 mA
Electronics module
or measuring cell de-
fective
Exchange the instrument or send it
in for repair
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
Error code Cause Rectication
E013 no measured value
available
8)
Exchange the instrument or send it
in for repair
E017 Adjustment span too
small
repeatwithmodiedvalues
E036 no operable sensor
software
Carry out a software update or send
instrument for repair
E041 Hardware error
Exchange the instrument or send it
in for repair
Depending on the reason for the fault and the measures taken, the
stepsdescribedinchapter"Set up"mayhavetobecarriedoutagain.
8.3 Exchanging the electronics module
In case of a defect, the electronics module can be exchanged by the
user against an identical type. If no electronics module is available on
side, the module can be ordered from the agency serving you.
Ordering and exchange are possible with or without sensor serial
number. The electronics module with serial number includes order-
specic data such as factory setting, seal material etc. These are not
included in the electronics module without serial number.
Error messages via the
display and adjustment
module
Reactionafterfaultrecti-
cation
8)
Fault message can also appear if the pressure is higher than the nominal
range.
Seitenansicht 44
1 2 ... 40 41 42 43 44 45 46 47 48 49 50 ... 67 68

Kommentare zu diesen Handbüchern

Keine Kommentare