48
10 Supplement
VEGABAR 55 • Foundation Fieldbus - climate compensated
39443-EN-130321
Nominalrange Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
0 … +150 psig +700 psig -15 psig
0 … +350 psig +700 psig -15 psig
-15 … 0 psig +500 psig -15 psig
-15 … +25 psig +700 psig -15 psig
-15 … +70 psig +700 psig -15 psig
-15 … +150 psig +700 psig -15 psig
-15 … +350 psig +700 psig -15 psig
-0.7 … +0.7 psig +200 psig -15 psig
-1.5 … +1.5 psig +290 psig -15 psig
-3 … +3 psig +430 psig -15 psig
-7 … +7 psig +500 psig -15 psig
Referenceconditionsandactuatingvariables(accordingtoDINEN60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ Temperature 18 … 30 °C (64 … 86 °F)
Ʋ Relative humidity 45 … 75 %
Ʋ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psi)
Determination of characteristics limit point adjustment according to DIN 16086
Characterstic curve Linear
Reference installation position upright, diaphragm points downward
Inuenceoftheinstallationposition < 5 mbar/0.5 kPa (0.07 psig)
Deviation determined according to the limit point method according to IEC 60770
10)
Applies to the digitalsignaloutput(HART,ProbusPA,FoundationFieldbus)aswellastoana-
logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
Deviation with version 0.075 %
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.075 %
Ʋ Turn down > 5 : 1 < 0.015 % x TD
Deviation with version 0.1 %
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.1 %
Ʋ Turn down > 5 : 1 < 0.02 % x TD
Deviation with version 0.2 %
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.2 %
Ʋ Turn down > 5 : 1 < 0.04 % x TD
Deviation with absolute pressure measuring range 0.1 bar
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.25 %
Ʋ Turn down > 5 : 1 < 0.05 % x TD
10)
Incl. non-linearity, hysteresis and non-repeatability.