Nominalrange Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
0 … +1.5 psig +200 psig -15 psig
0 … +3 psig +290 psig -15 psig
0 … +6 psig +430 psig -15 psig
0 … +15 psig +500 psig -15 psig
0 … +35 psig +700 psig -15 psig
0 … +70 psig +950 psig -15 psig
0 … +150 psig +1300 psig -15 psig
0 … +350 psig +1900 psig -15 psig
0 … +900 psig +2900 psig -15 psig
Absolute pressure
0 … 15 psi 500 psi 0 psi
0 … 35 psi 700 psi 0 psi
0 … 70 psi 900 psi 0 psi
0 … 150 psi 1300 psi 0 psi
0 … 350 psi 1900 psi 0 psi
Referenceconditionsandactuatingvariables(accordingtoDINEN60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ Temperature 18 … 30 °C (64 … 86 °F)
Ʋ Relative humidity 45 … 75 %
Ʋ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psi)
Determination of characteristics limit point adjustment according to DIN 16086
Characterstic curve Linear
Reference installation position upright, diaphragm points downward
Inuence of the installation position
< 5 mbar/0.5 kPa (0.07 psig)
Deviation determined according to the limit point method according to IEC 60770
12)
Applies to the digital signal output (HART, Probus PA, Foundation Fieldbus) as well as to ana-
logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
Deviation
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.1 %
Ʋ Turn down > 5 : 1 < 0.02 % x TD
Inuenceoftheproductorambienttemperature
Thermal change zero signal and output span
Applies to the digital signal output (HART, Probus PA, Foundation Fieldbus) as well as to ana-
logue
current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
Thermal change zero signal and output span, reference temperature 20 °C (68 °F):
12)
Incl. non-linearity, hysteresis and non-repeatability.