32 VEGAPULS 43 – Profibus PA
Electrical connection
Example 2
You want to set address 27.
16 + 8 + 2 + 1 = 27
You must set the DIP switches
5 = 16
4 = 8
2 = 2
1 = 1
to „ON“.
Example 3
You want to set address 99
64 + 32 + 2 + 1 = 99
You must set the DIP switches
7 = 64
6 = 32
2 = 2
1 = 1
to „ON.
Software addressing
The DIP switches must be set to an address
of 126 … 255, i.e.
- either all DIP switches are set to „ON“,
corresponding to address 255 (delivery
status)
- or only DIP switch 8 is set to „ON“, corre-
sponding to address 128.
Of course, software addressing is also pos-
sible if the switches 7 2 are set to „ON“
(address 126).
The adjustment of the address with the soft-
ware VVO is described in chapter “5.2 Ad-
justment with VVO” under the heading
“Software addressing” or in chapter “5.3
Sensor adjustment with the adjustment mod-
ule MINICOM”.
ON
Addr.
87654
3
2
1
OFF
1
2
4
8
16
32
64
128
87654
3
2
1