53
9 Diagnosis, Asset Management and service
VEGAPULS 62 • 4 … 20 mA/HART - four-wire
36504-EN-121011
Further echo curves: Up to 10 echo curves can be stored in a ring
buer in this memory section. Further echo curves are stored via:
•
PC with PACTware/DTM
•
Control system with EDD
9.3 Asset Management function
The instrument features self-monitoring and diagnostics according
to NE 107 and VDI/VDE 2650. In addition to the status messages in
the following tables there are more detailed error messages available
under the menu item "Diagnostics" via the indicating and adjustment
module, PACTware/DTM and EDD.
The status messages are classied in the following categories:
•
Failure
•
Function check
•
Out of specication
•
Maintenance requirement
and explained by pictographs:
41 2 3
Fig. 35: Pictograms of the status messages
1 Failure - red
2 Function check - orange
3 Outofspecication-yellow
4 Maintenance - blue
Failure: Due to a malfunction in the instrument, a failure message is
outputted.
This status message is always active. It cannot be deactivated by the
user.
Function check: The instrument is in operation, the measured value
is temporarily invalid (for example during simulation).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Outofspecication: The measured value is unstable because the
instrument specication is exceeded (e.g. electronics temperature).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Maintenance: Due to external inuences, the instrument function
is limited. The measurement is aected, but the measured value is
still valid. Plan in maintenance for the instrument because a failure is
expected in the near future (e.g. due to buildup).
This status message is inactive by default. It can be activated by the
user via PACTware/DTM or EDD.
Status messages