VEGACOM 557 Profibus FMS 17
Addressing of the process signals
DIL switch 1, additional board
Adjustment of the baud rate
Baud rate
(kBit/s) S8 S7 S6 S5 S4 S3 S2 S1
9.6 off off off off off off off off
19.2 off off off off off off off on
93.75 off off off off off off on off
187.5 off off off off off off on on
500 off off off off off on off off
1500 off off off off off on off on
DIL switch 2, additional board
PROFIBUS address of VEGACOM 557
SW 8 SW 7 SW 6 SW 5 SW 4 SW 3 SW 2 SW 1
2
7
2
6
2
5
2
4
2
3
2
2
2
1
2
0
Example: = Address 32
SW 8 SW 7 SW 6 SW 5 SW 4 SW 3 SW 2 SW 1
off off on off off off off off
Hook switch, additional board
The hook switches are used to switch on the
bus termination resistances.
Switch positions
L R
1
L R
2
L R
1
L R
2
Bus termination "on"
Bus termination "off"
Note:
L = position left,
R = position right
Example 1
VEGACOM 557
PLC
Both hook switches "on"
If one VEGACOM 557 is connected to one
PlC, the hook switches must be set to posi-
tion "on" (bus termination on).
Example 2
VEGACOM 557
VEGACOM 557
PLC
Both hook switches:
on off off on
If several VEGACOM 557 are connected to
oneone
oneone
one PLC, the hook switches at the beginning
and end of the cable have to be in position
"on" (VEGACOM), and in position "off" on
VEGACOM 557 located in between.
3.2 Factory set switch position
DIL switch, basic board
DIL switch and hook switch, additional
board
1
ON EDG
23456
Transmission rate: 9.600 baud
1
ON EPG
2345678 1
ON EPG
2345678
DIL switch 2
DIL switch 1
L R
1
L R
2
Bus termination "off"