30 VEGACOM 557 Profibus FMS
Setup
FB245: RECEIVE component
The functional component FB245 gives a receive order to the CP. A difference is made be-
tween the orders RECEIVE and RECEIVE_ALL. With RECEIVE_ALL (A-NR is 0) receipt data of
individual emission orders are received and the order RECEIVE_ALL is recommended here to
read in measured values. The information in which data component the received data should
be saved, was provided previously with the transmission order. Therefore no further param-
eters are necessary for RECEIVE_ALL.
Important:
To ensure that the receive data can be always accepted from AG, the FB245 (RECEIVE_ALL)
must be called up with each program cycle, even if no transmission order was given immedi-
ately before.
FB245: RECEIVE_ALL (A-NR=0)
Parameter Format Description Example
SSNR KY Interface number KY 0,0
A-NR KY Order number KY 0,0
ANZW MW Indication value MW 2
QTYP KC Source type : Data component KC NN
DBNR KY Data component number KY 0,0
QANF / ZANF KY Relative initial address within the type KY +0
QLAE / ZLAE KF Number of source/destination data KF +0
PAFE MB Parameter setting error MB 255
In this example, received data are transferred to AG
4.4.4 FB247: CONTROL component
With the CONTROL component, the indication word ANZW and the failure indication PAFE are
updated. Status in failure information can be read in for further processing.
This FB must be applied before calling up a transmission order (FB244). FB244 must be called
up only if no transmission order is running. This is done by evaluation of the indicating word.
This prevents the transmission order from not being accepted due to an inadmissible CP
status.
FB247: CONTROL
Parameter Format Description Example
SSNR KY Interface number KY 0,0
A-NR KY Order number KY 0,1
ANZW MW Indication value MW 2
PAFE MB Parameter setting error MB 255
In this example, the current indication word is saved in marker word 2 and the current failure
indication in marker byte 255.