6 Set up with the display and adjustment module
MINITRAC 31 • 4 … 20 mA/HART - four-wire
40447-EN-131119
Linearization-Modify
Youcanalsomodifyindividuallinearizationpoints.
After editing, you have to activate the complete value pair so that the
linearizationpointwillbeeective.
Yourecognizeactivelinearizationpointsbyasmallsquarewitha
crossnexttothenumberofthelinearizationpoint.
In this menu item you can adjust the damping of the sensor. With
ityoucansuppressuctuationsinthemeasuredvalueindication,
caused e.g. by an agitated product surface. This time can be between
1 and 1200 seconds. Keep in mind that the reaction time also in-
creases and the instrument reacts to quick level changes with a delay.
Generallyatimeofapproximately60secondsissucienttosmooth
the measured value indication.
With the setting "Automatic", the instrument itself calculates a suitable
damping on the basis of the adjustment and the measured value
changes. This setting is particularly suitable for application where fast
and slow level changes occur.
The implementation of a real value corretion is only necessary if the
requirements of the measurement loop have changed, for example
with abrasion in a tube.
If you know the density of a certain medium, you can enter the deter-
mined real density in this menu item to correct the measured value.
Thefunctionshiftsthelinearizationcurvetothisdeterminedpoint.
The measurement can thus be adapted exactly to the conditions in
the tube.
Setup/Damping
Setup/Real value correc-
tion (manually)