28
5 Connecting to power supply
MINITRAC 31 • Probus PA
43836-EN-131119
5.4 Set instrument address
An address must be assigned to each Probus PA instrument. The
approved addresses are between 0 and 126. Each address must
only be assigned once in the Probus PA network. The sensor is only
recognized by the control system if the address is set correctly.
When the instrument is shipped, address 126 is adjusted. This ad-
dress can be used for function test of the instrument and for con-
nection to a Probus PA network. Then address must be changed to
integrate additional instruments.
The address setting is carried out either via:
•
The address selection switch in the electronics compartment of
the instrument (address setting via hardware)
•
The display and adjustment module (address setting via software)
•
PACTware/DTM (address setting via software)
The hardware addressing is eective if an address <126 is adjusted
with the address selection switches on the instrument. Hence the
software addressing is no longer eective, the adjusted hardware
address is valid.
1
1
2456
22
11
12
2122 1920 18 17 14 1316 15 12
91011
Fig. 18: Address selection switch
1 Addresses <100 (selection 0), addresses >100 (selection 1)
2 Decade of the address (selection 0 to 9)
3 Unitpositionoftheaddress(selection0to9)
The software addressing is only eective if address 126 or higher is
adjusted on the instrument with the address selection switches.
The addressing procedure is described in the operating instructions
manual "Display and adjustment module.
Instrument address
Hardware addressing
Software addressing