13
4 Mounting
VEGABAR 54 • Probus PA
36729-EN-130321
Warning:
The housing must not be used to screw the instrument in! Applying
tightening force can damage internal parts of the housing.
Seal the ange connections according to DIN/ANSI with a suitable,
resistant seal and mount VEGABAR 54 with suitable screws.
Use the seal corresponding to the instrument.
→
Shift VEGABAR 54 with PMC connection into the socket and
fasten with two screws M8x10.
4.3 Mounting steps, external housing
1. Mark the holes according to the following drilling template
2. Depending on the mounting surface, fasten the wall mounting
plate with 4 screws
90 mm (3.54")
R 3,5 mm
(0.14")
3mm
(0.12")
70 mm (2.76")
8 mm
(0.32")
93 mm (3.66")
110 mm (4.33")
Fig. 4: Drilling template - wall mounting plate
Tip:
Mount the wall mounting plate so that the cable entry of the socket
housing points downward. The socket housing can be displaced by
180° to the wall mounting plate.
Warning:
The four screws of the socket housing must only be hand screwed. A
torque > 5 Nm (3.688 lbf ft) can damage the wall mounting plate.
Sealing/Screwing in
angeversions
Mounting, socket ver-
sions
Wall mounting