10 Supplement
VEGABAR 54 • Probus PA
36729-EN-130321
Nominalrange Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
0 … 900 psi 2900 psi 0 psi
Referenceconditionsandactuatingvariables(accordingtoDINEN60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ Temperature +15 … +25 °C (+59 … +77 °F)
Ʋ Relative humidity 45 … 75 %
Ʋ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Determination of characteristics Limit point adjustment according to IEC 61298-2
Characterstic curve Linear
Reference installation position upright, diaphragm points downward
Inuence of the installation position
< 0.2 mbar/20 Pa (0.003 psig)
Deviation determined according to the limit point method according to IEC 60770
10)
Applies to the digital signal output (HART, Probus PA, Foundation Fieldbus) as well as to ana-
logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
Deviation with version 0.1 %
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.1 %
Ʋ Turn down > 5 : 1 < 0.02 % x TD
Deviation with version 0.2 %
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.2 %
Ʋ Turn down > 5 : 1 < 0.04 % x TD
Inuenceoftheproductorambienttemperature
Averagetemperaturecoecientofthezerosignal
Applies to the digital signal output (HART, Probus PA, Foundation Fieldbus) as well as to ana-
logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
In the compensated temperature range 0 … +100 °C (+32 … +212 °F), reference temperature
20 °C (68 °F).
Average temperature coecient zero signal
Ʋ Turn down 1 : 1 < 0.05 %/10 K
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.1 %/10 K
Ʋ Turn down up to 10 : 1 < 0.15 %/10 K
Outside the compensated temperature range:
Average temperature coecient zero signal
Ʋ Turn down 1 : 1 typ. < 0.05 %/10 K
Thermal change of the current output
Applies also to the analogue
4 … 20 mA current output and refers to the set span.
Thermal change, current output < 0.05 %/10 K, max. < 0.15 %, each with -40 … +80 °C
(-40 … +176 °F)
10)
Incl. non-linearity, hysteresis and non-repeatability.