47
10 Supplement
VEGABAR 54 • Probus PA
36729-EN-130321
Nominalrange Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
0 … 900 psi 2900 psi 0 psi
Referenceconditionsandactuatingvariables(accordingtoDINEN60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ Temperature +15 … +25 °C (+59 … +77 °F)
Ʋ Relative humidity 45 … 75 %
Ʋ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Determination of characteristics Limit point adjustment according to IEC 61298-2
Characterstic curve Linear
Reference installation position upright, diaphragm points downward
Inuence of the installation position
< 0.2 mbar/20 Pa (0.003 psig)
Deviation determined according to the limit point method according to IEC 60770
10)
Applies to the digital signal output (HART, Probus PA, Foundation Fieldbus) as well as to ana-
logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
Deviation with version 0.1 %
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.1 %
Ʋ Turn down > 5 : 1 < 0.02 % x TD
Deviation with version 0.2 %
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.2 %
Ʋ Turn down > 5 : 1 < 0.04 % x TD
Inuenceoftheproductorambienttemperature
Averagetemperaturecoecientofthezerosignal
Applies to the digital signal output (HART, Probus PA, Foundation Fieldbus) as well as to ana-
logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
In the compensated temperature range 0 … +100 °C (+32 … +212 °F), reference temperature
20 °C (68 °F).
Average temperature coecient zero signal
Ʋ Turn down 1 : 1 < 0.05 %/10 K
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.1 %/10 K
Ʋ Turn down up to 10 : 1 < 0.15 %/10 K
Outside the compensated temperature range:
Average temperature coecient zero signal
Ʋ Turn down 1 : 1 typ. < 0.05 %/10 K
Thermal change of the current output
Applies also to the analogue
4 … 20 mA current output and refers to the set span.
Thermal change, current output < 0.05 %/10 K, max. < 0.15 %, each with -40 … +80 °C
(-40 … +176 °F)
10)
Incl. non-linearity, hysteresis and non-repeatability.