6 Set up with the display and adjustment module PLICSCOM
VEGABAR 54 • Probus PA
36729-EN-130321
Linearization curve
Sensor-TAG
Displayed value
Scaling unit (Out-Scale unit)
Positions after the decimal point (scaled)
Scaling PA/Out-Scale 4 values
Unit of measurement
Language
The following safety-relevant data are not read out or written:
Sensor address
PIN
Application
Copy sensor data
Copy sensor data?
The reset function resets all parameters adjusted by the user to the
delivery status and the peak values to the actual values.
Reset
Select reset?
Reset
Basic adjustment
Peak value, measured value
Peak value, temperature
Basic adjustment
The "Reset" "Basic adjustment" resets the values of the following
menu items:
Menu section Function Resetvalue
Basic settings Sensor address 126
Zero/Min. adjustment Measuring range begin
Span/Max. adjustment Measuring range end
Density
1 kg/l
Density unit kg/l
Damping
0 s
Linearization Linear
Sensor-TAG Sensor
Display Displayed value PA-Out
Service Additional PA value Secondary Value 1
Out-Scale-Unit Volume/l
Scaling 0.00 to 100.0
Reset