6 Set up with the display and adjustment module PLICSCOM
VEGABAR 66 • Foundation Fieldbus
36740-EN-130321
Proceed as follows:
1. Editthembarvalueinthemenuitem"span"with[OK].
Span
100.0 %
P
=
+1000.0 mbar
0000.0 mbar
Information:
The displayed pressure for 100 % corresponds to the nominal meas-
uring range of the sensor (in the above example 1 bar = 1000 mbar).
2. Set the requested mbar value with [->] and [OK].
3. Conrmwith[OK] and move to the menu overview with [ESC].
Thespanadjustmentisnished.
Information:
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
Iftheadjustmentrangesareexceeded,themessage"Outside param-
eter limits"appears.Theeditingprocedurecanbeabortedwith[ESC]
or the displayed limit value can be accepted with [OK].
This function enables reading out parameter adjustment data as well
as writing parameter adjustment data into the sensor via the display
and adjustment module. A description of the function is available in
theoperatinginstructionsmanual"Display and adjustment module".
The following data are read out or written with this function:
Measured value presentation
Adjustment
Damping
Linearizationcurve
Sensor-TAG
Displayed value
Unitofmeasurement
Language
The following safety-relevant data are not read out or written:
PIN
Application
Copy sensor data
Copy sensor data?
The reset function resets all parameters adjusted by the user to the
delivery status and the peak values to the actual values.
Reset
Select reset?
Carry out span adjust-
ment
Copy sensor data
Reset