6 Set up with the display and adjustment module
VEGABAR 81 • Modbus and Levelmaster protocol
46293-EN-131107
4. Move with [ESC] and [->] to the span adjustment
Thezeroadjustmentisnished.
Information:
Thezeroadjustmentshiftsthevalueofthespanadjustment.The
span,i.e.thedierencebetweenthesevalues,however,remains
unchanged.
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
If the adjustment ranges are exceeded, the message "Outside param-
eter limits" appears. The editing procedure can be aborted with [ESC]
or the displayed limit value can be accepted with [OK].
Proceed as follows:
1. Select with [->]themenuitem"Spanadjustment"andconrm
with [OK].
2. Edit the mbar value with [OK] and set the cursor to the requested
position with [->].
3. Set the requested mbar value with [+] and store with [OK].
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
If the adjustment ranges are exceeded, the message "Outside param-
eter limits" appears. The editing procedure can be aborted with [ESC]
or the displayed limit value can be accepted with [OK].
Thespanadjustmentisnished.
Proceed as follows:
1. Select the menu item "Setup" with [->]andconrmwith[OK].
Now select with [->] the menu item "Adjustment", then "Min.
adjustment"andconrmwith[OK].
2. Edit the percentage value with [OK] and set the cursor to the
requested position with [->].
3. Set the requested percentage value (e.g. 10 %) with [+] and save
with [OK]. The cursor jumps now to the pressure value.
4. Enter the pressure value corresponding to the min. level (e.g.
0 mbar).
Setup - span adjustment
Setup - Min. adjustment
Level