Vega VEGABAR 81 Modbus and Levelmaster protocol - Opera Bedienungsanleitung Seite 79

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 92
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 78
79
10 Supplement
VEGABAR 81 • Modbus and Levelmaster protocol
46293-EN-131107
ScadaPack
Wiring plan
+
+
power supply
MODBUS
D0
D1
IS GND
USB
1
3
2
13
45
5
2
1
3
4
9
6
7
8
2off
on
( )
( )
(-)
(-)
+8 +30
Vdc
to
GND
COM Part 3 (C3)
RS485
TXD-
TXD+
GND
Fig. 38: Connection of VEGABAR 81 to RTU ScadaPack
1 VEGABAR 81
2 RTU ScadaPack
3 Voltage supply
Parameter
Parameter Value
Baud Rate 9600
Floating Point Format Code 0
RTU Data Type Floating Point
Input Register Base Number 30001
The basic number of the input registers is always added to the input register address of VEGABAR
81.
Address 31303 must hence be entered as register address for 1302 for RTU ScadaPack.
10.7 Dimensions
The following dimensional drawings represent only an extract of the possible versions. Detailed
Seitenansicht 78