Vega Conductive electrodes Bedienungsanleitung Seite 29

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 40
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 28
Conductive measuring system 29
Set-up
1
2
3
1
2
3
Selection of mode A/B
A slide switch (16 and 17) per channel is
located on the circuit board of the signal
conditioning instrument. Position A
corresponds to overfill protection, position B
to dry run protection.
Failure adjustment (soldering bridges)
For monitoring of the electrodes and their
circuits, a resistor of 220 kOhm must be
mounted between connection 1 and
connection 2 in the connection housing of the
electrode, i.e. with single point control
measuring and mass electrodes are
monitored and with double point control max.
and mass electrode.
For electrodes without 220 kOhm resistor, a
soldering bridge must be closed on the
circuit board on the multipoint connector of
the signal conditioning instrument
- relating to channel 1 = bridge BR1 (14)
- relating to channel 2 = bridge BR2 (15).
Note
With closed soldering bridge the line
monitoring and appropriate fault signal are
inactive.
If a measuring system is used as part of an
overfill protection, the appropriate soldering
bridge must not be closed.
With Ex-electrodes of VEGA this resistor is
already available as a standard feature.
Selection of the mode
By means of the two selection switches (16
and 17) mode A or B can be adjusted
separately for each channel.
Mode A
preferably as overflow protection
compulsorily as overfill protection
means with covered max.-electrode
- relay of output 1 deenergizes,
connection d10 - b10 are connected
through relays
- transistor output 1 blocks
- LED output 1 extinguishes
means with uncovered max.-electrode (level
detection) or min.-electrode (pump control)
- relay of output 1 energizes,
connection d10 - z10 is connected through
relays
- transistor output 1 is conductive
- LED relay output 1 lights
Mode B
preferably as dry run protection
means with covered max.-electrode
- relay of output 1 energizes,
connection d10 - z10 is connected through
relays
- transistor output 1 is conductive
- LED output 1 lights
means with uncovered max.-electrode (sin-
gle point control) or min.-electrode (double
point control)
- relay of output 1 deenergizes,
connection d10 - b10 is connected through
relays
- transistor output 1 blocks
- LED output 1 extinguishes