Pressure transmitters D86/D87 25
Setup
The most important adjustment steps
On the following four pages you see a menu
schematic of the HART
®
handheld in conjunc-
tion with pressure transmitters D80 D87.
The most important adjustment steps are
marked in the menu schematic with the letters
A D. If you are not familiar with HART
®
handheld, please note:
After entering a parameter, first push the
"
ENTER
" key. The adjustment is saved in the
handheld, but not in the sensor itself.
After you have pushed "
ENTER
", you have to
push "
SEND
" (here in the example for the
min. adjustment), to transfer the input to the
sensor.
After pushing "
SEND
", a warning is displayed
that you are about to change device output
and for safety reasons, you should switch
your system to manual operation. Push "
OK
"
and the adjustment is now transferred to the
sensor.
After a moment, you are asked to switch the
system from manual to automatic operation.
Confirm with "
OK
"
and then with "
HOME
".
You are now in the initial menu.
Generic: SENSOR
PV LVR
0.000 mbar
10.000 mbar
HELP DEL ESC ENTER
Generic: SENSOR
1 PV LRV
2 PV URV
HELP SEND HOME
4.1
(5.1)
Empty adjustment without
medium
Generic: SENSOR
WARNING
Pressing „OK“ will
change device output
Put loop in manual
ABORT OK
Generic: SENSOR
Online (general)
1 Sensor unit
2 PV 80.945 mbar
3 PV Analog output
4 PV LRV
5 PV URV
HELP SAVE
Generic: SENSOR
1 PV LRV
2 PV URV
HELP HOME
Generic: SENSOR
WARNING
Return control loop to
automatic control
OK