6 Set up with the display and adjustment module
FIBERTRAC 31 • Probus PA
43833-EN-131119
In menu item "Scaling unit" you dene the scaling variable and the
scaling unit for the pulse rate on the display, e.g. volume in percent.
In menu item "Scaling" you dene the scaling format on the display
and the scaling of the measured values for 0 % and 100 %.
Measured value min.
Measured value max.
To damp process-dependent measured value uctuations, you can
set a time of 0 … 999 s in this menu item.
The default setting is a damping of 0 s.
In this menu item you can adjust the damping of the sensor. With
it you can suppress uctuations in the measured value indication,
caused e.g. by an agitated product surface. This time can be between
1 and 1200 seconds. Keep in mind that the reaction time also in-
creases and the instrument reacts to quick level changes with a delay.
Generally a time of approximately 60 seconds is sucient to smooth
the measured value indication.
With the setting "Automatic", the instrument itself calculates a suitable
damping on the basis of the adjustment and the measured value
changes. This setting is particularly suitable for application where fast
and slow level changes occur.