14 VEGABAR 20
4.1 Adjustment of the basic
functions
Adjustment elements
OPERATE
t
SPAN
ZERO
i
Key +: Change
value (raising)
Key : Change
value (lowering)
Rotating switch: Select re-
quired function
Set-up
Indicating module
VEGABAR
87654321
4 ¼ 20 mA
DISPLAY
VEGADIS 10
12 ¼ 36 V DC E12
+ -
+
-
OK
0 - 20 bar
Loosely tighten screws
4 Set-up
Electrical connection and set-up can be sim-
plified by temporarily mounting the cover or
indicating module on VEGABAR or laterally
displaced downwards.
Adjustment system
Select the required function with the rotat-
ing switch.
Change the value with keys “+“- and “–“.
Reset rotating switch to OPERATE, the
adjusted values are transferred to the
EEPROM-memory. They remain there even
on voltage loss.
Adjustment
For adjustment of zero and span, a current
meter must be connected to terminals 1 and
3. The measured value is identical with the
output current.
1 Adjustment of zero
(e.g. process pressure zero or empty
vessel)
Set rotating switch to zero
By pushing the “+“ and “–“-keys simultane-
ously, the current jumps directly to 4 mA or
set it to 4 mA by pushing the “+“ and “–“-
keys
Adjustment range of zero:
-20 % +95 % of the nominal measuring
range (corresponds to turn up of up to
+95 %)
2 Adjustment of span
(e.g. process pressure or vessel level
maximum)
Set rotating switch to span
By pushing the “+“ and “–“-keys simultane-
ously, the current jumps directly to 20 mA
or set it to 20 mA by pushing the “+“ and “–
-keys
Adjustment range of span:
3,3 % 120 % of the nominal measuring
range (corresponds to turn down 1 : 30)
Note:
- A modification of zero does not influence
the span.
- It is also possible to adjust currents for
partial fillings or partial pressures, e.g.
8 mA for 25 % and 16 mA for 75 %. VEGA-
BAR automatically calculates the current
values for 0 % or 100 % (only possible with
³ 3,3 %).