8Maintenanceandfaultrectication
VEGABAR 54 • 4 … 20 mA/HART
36726-EN-130321
Error code Cause Rectication
4 … 20 mA
signal not
stable
Leveluctuations – Set the integration time via the
display and adjustment module or
PACTware
No atmospheric pres-
sure compensation
– Check the pressure compensation
inthehousingandcleanthelter
element, if necessary
4 … 20 mA
signal miss-
ing
Connection to volt-
age supply wrong
– Check connection according to
chapter"Connection steps"and
if necessary, correct according to
chapter"Wiring plan"
No power supply
– Check cables for breaks; repair if
necessary
Operating voltage
too low or load resist-
ance too high
– Check, adapt if necessary
Current sig-
nal greater
than 22 mA
or less than
3.6 mA
Electronics module
or measuring cell de-
fective
– Exchange the instrument or send it
in for repair
In Ex applications, the regulations for the wiring of intrinsically safe
circuits must be observed.
Error code Cause Rectication
E013 no measured value
available
8)
– Exchange the instrument or send it
in for repair
E017 Adjustment span too
small
– repeatwithmodiedvalues
E036 no operable sensor
software
– Carry out a software update or send
instrument for repair
E041 Hardware error
– Exchange the instrument or send it
in for repair
Depending on the reason for the fault and the measures taken, the
stepsdescribedinchapter"Set up"mayhavetobecarriedoutagain.
8.3 Calculation of total deviation (according to
DIN16086)
The total deviation F
total
according to DIN 16086 is the sum of basic
accuracy F
perf
and longterm stability F
stab
. F
total
is also called maximum
practical deviation or utility error.
F
total
= F
perf
+ F
stab
F
perf
=√((F
T
)
2
+ (F
Kl
)
2
)
With the analogue signal output there is also the error of the current
output F
a
.
Error messages via the
display and adjustment
module
Reactionafterfaultrecti-
cation
Total deviation
8)
Fault message can also appear if the pressure is higher than the nominal
range.