Vega VEGABAR 55 Profibus PA Bedienungsanleitung Seite 32

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 68
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 31
32
6 Set up with the display and adjustment module PLICSCOM
VEGABAR 55 • Probus PA
36735-EN-130321
4. Activate the selection with [OK] and select the requested unit with
[->] (in the example mbar).
5. Conrm with [OK] and move to position correction with [->].
The adjustment unit is thus switched over from bar to mbar.
Proceed as follows to select the temperature unit:
6)
1. Activate the selection with [OK] and select "Temperature unit
with [->].
2. Activate the selection with [OK] and select the requested unit with
[->] (e.g. °F).
3. Conrm with [OK].
The temperature unit is hence switched over from °C to °F.
Proceed as follows:
1. Activate in the menu item "Position correction" the selection with
[OK].
Position correction
Oset
P
=
+0000 mbar
53 mbar
2. Select with [->], e.g. to accept actual measured value.
Position correction
Accept current measured
value?
Accept
Edit
3. Conrm with [OK] and move to min.(zero) adjustment with [->].
Proceed as follows:
1. Edit the mbar value in the menu item "zero" with [OK].
Zero
000.0 %
P
=
+0000.0 mbar
0000.0 mbar
2. Set the requested mbar value with [+] and [->].
3. Conrm with [+] and move to span adjustment with [->].
The zero adjustment is nished.
Information:
The zero adjustment shifts the value of the span adjustment. The
span, i.e. the dierence between these values, however, remains
unchanged.
Information:
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
Carry out a position cor-
rection
C
arrying out zero adjust-
ment
6)
Selection options: °C, °F.
Seitenansicht 31
1 2 ... 27 28 29 30 31 32 33 34 35 36 37 ... 67 68

Kommentare zu diesen Handbüchern

Keine Kommentare