Operating InstructionsPressure transmitter with METEC® measuring cellVEGABAR 55Probus PADocument ID: 36735
103 Product descriptionVEGABAR 55 • Probus PA36735-EN-130321• with the adjustment program PDM3.4 Packaging, transport and storageYour instrument was
113 Product descriptionVEGABAR 55 • Probus PA36735-EN-130321VEGADIS 61 is suitable for external measured value indication and adjustment of plics® se
124 MountingVEGABAR 55 • Probus PA36735-EN-1303214 Mounting4.1 General instructionsMake sure that all parts of the instrument coming in direct conta
134 MountingVEGABAR 55 • Probus PA36735-EN-13032121212112Fig. 4: Position of the lter element1 Filter element2 Blind plugCaution:Due to the lter
144 MountingVEGABAR 55 • Probus PA36735-EN-1303214.2 Mounting stepsFor mounting VEGABAR 55, a welded socket is required. You can nd these component
155 Connecting to power supplyVEGABAR 55 • Probus PA36735-EN-1303215 Connecting to power supply5.1 Preparing the connectionAlways keep in mind the
165 Connecting to power supplyVEGABAR 55 • Probus PA36735-EN-130321next distributor must be connected to each other and also connected to ground pote
175 Connecting to power supplyVEGABAR 55 • Probus PA36735-EN-130321Fig. 7: Connection steps 6 and 7Proceed as follows:1. Loosen the four screws on t
185 Connecting to power supplyVEGABAR 55 • Probus PA36735-EN-130321Information:The cable gland can be mounted in three positions each displaced by 90
195 Connecting to power supplyVEGABAR 55 • Probus PA36735-EN-130321I2CDisplay112 5 678Fig. 10: Wiring plan, single chamber housing1 Voltage supply,
2ContentsVEGABAR 55 • Probus PA36735-EN-130321Contents1 About this document1.1 Function ...
205 Connecting to power supplyVEGABAR 55 • Probus PA36735-EN-130321123Display12I2CFig. 12: Connection compartment, double chamber housing1 Spring-lo
215 Connecting to power supplyVEGABAR 55 • Probus PA36735-EN-130321132Display12 5678I2CFig. 15: Electronics compartment, double chamber housing1 Plu
225 Connecting to power supplyVEGABAR 55 • Probus PA36735-EN-130321112Fig. 17: Wiring plan, Ex-d double chamber housing1 Voltage supply, signal outp
235 Connecting to power supplyVEGABAR 55 • Probus PA36735-EN-130321567812DisplayI²C21543Fig. 20: Electronics and connection compartment1 Spring-load
245 Connecting to power supplyVEGABAR 55 • Probus PA36735-EN-1303211234634125Fig. 21: Connection of the sensor in the housing socket1 Brown2 Blue3
256 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-1303216 Set up with the display and adjustment module PLICS
266 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-130321Fig. 23: Insert display and adjustment moduleNote:If y
276 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-130321 – Save value• [->] key to select: – Menu change –
286 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-130321The display and adjustment module enables the adjustme
296 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-1303215. Select the requested unit, e.g. kg/dm³ with [->
3ContentsVEGABAR 55 • Probus PA36735-EN-1303218 Maintenanceandfaultrectication8.1 Maintain ...
306 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-130321Information:For an adjustment with lling, simply ente
316 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-130321You can nd the data on the type label on the instrume
326 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-1303214. Activate the selection with [OK] and select the re
336 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-130321If the adjustment ranges are exceeded, the message &qu
346 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-130321This function enables reading out parameter adjustment
356 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-130321Menu section Function ResetvalueDamping 0 sLinearizat
366 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-130321Basic adjustment▶Basic adjustment 1DisplayDiagnosticsS
376 Set up with the display and adjustment module PLICSCOMVEGABAR 55 • Probus PA36735-EN-130321ServiceBasic adjustment 4DisplayDiagnostics▶ServiceInf
387 Set up with PACTware and other adjustment programsVEGABAR 55 • Probus PA36735-EN-1303217 Set up with PACTware and other adjustment programs7.1
397 Set up with PACTware and other adjustment programsVEGABAR 55 • Probus PA36735-EN-1303217.2 Parameter adjustment with PACTwareFurther setup steps
41 About this documentVEGABAR 55 • Probus PA36735-EN-1303211 About this document1.1 FunctionThis operating instructions manual provides all the info
408 Maintenance and fault recticationVEGABAR 55 • Probus PA36735-EN-1303218 Maintenanceandfaultrectication8.1 MaintainIf the instrument is used
418 Maintenance and fault recticationVEGABAR 55 • Probus PA36735-EN-130321Error Cause RecticationWhen an addi-tional instrument is connected, the s
428 Maintenance and fault recticationVEGABAR 55 • Probus PA36735-EN-130321Error code Cause RecticationE113 Communication con-ict – Exchange the in
438 Maintenance and fault recticationVEGABAR 55 • Probus PA36735-EN-130321Total deviation digital output signal absolute:Ftotal = 0.315 % x 8 bar/10
448 Maintenance and fault recticationVEGABAR 55 • Probus PA36735-EN-130321At "www.vega.com/downloads" go to "Software". Select u
459 DismountingVEGABAR 55 • Probus PA36735-EN-1303219 Dismounting9.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous process cond
4610 SupplementVEGABAR 55 • Probus PA36735-EN-13032110 Supplement10.1 Technical dataGeneral dataPressure type Gauge pressure, absolute pressure, vac
4710 SupplementVEGABAR 55 • Probus PA36735-EN-130321 Ʋ Connection cable with IP 68 1 bar versionPE, PURWeight approx.0.8 … 8 kg (1.764 … 17.64 lbs),
4810 SupplementVEGABAR 55 • Probus PA36735-EN-130321The specications are only an overview and refer to the measuring cell. Limitations due to the ma
4910 SupplementVEGABAR 55 • Probus PA36735-EN-130321Nominalrange Overload capacity, max. pressureOverload capacity, min. pres-sure0 … +70 psig +700
52 For your safetyVEGABAR 55 • Probus PA36735-EN-1303212 For your safety2.1 Authorised personnelAll operations described in this operating instruct
5010 SupplementVEGABAR 55 • Probus PA36735-EN-130321 Ʋ Turn down > 5 : 1 < 0.02 % x TDDeviation with version 0.2 % Ʋ Turn down 1 : 1 up to 5 :
5110 SupplementVEGABAR 55 • Probus PA36735-EN-130321Ambient conditionsAmbient, storage and transport temperature Ʋ Standard version -40 … +80 °C (-40
5210 SupplementVEGABAR 55 • Probus PA36735-EN-130321 Ʋ Double chamber housing – 1 x cable entry M20 x 1.5 (cable: ø 5 … 9 mm), 1 x blind plug M20 x
5310 SupplementVEGABAR 55 • Probus PA36735-EN-130321 Ʋ Diameter approx. 8 mm (0.315 in) Ʋ Colour BlueCable entry/plug14) Ʋ External housing – 1 x ca
5410 SupplementVEGABAR 55 • Probus PA36735-EN-130321 Ʋ External housing IP 65, IP 66/IP 68 (0.2 bar)Overvoltage category IIIProtection class IIApprov
5510 SupplementVEGABAR 55 • Probus PA36735-EN-130321bar% Lin%Min-MaxadjustmentLinearizationPROFIBUS PA-outputPrimaryValueSecondaryValue 1SecondaryVal
5610 SupplementVEGABAR 55 • Probus PA36735-EN-130321ExamplesoftelegramcongurationIn the following you will see how the modules can be combined an
5710 SupplementVEGABAR 55 • Probus PA36735-EN-130321Byte nByte n+1Bit7VZExponentBit62Bit52Bit42Bit32Bit22Bit12Bit02Bit72Bit62Bit52Bit42Bit32Bit22Bit1
5810 SupplementVEGABAR 55 • Probus PA36735-EN-13032110.3 DimensionsPlastic housing~ 69 mm(2.72")ø 79 mm(3.03")112 mm (4.41")M20x1,5/½
5910 SupplementVEGABAR 55 • Probus PA36735-EN-130321AluminiumhousinginprotectionratingIP66/IP68(1bar)120 mm (4.72")~ 105 mm (4.13"
62 For your safetyVEGABAR 55 • Probus PA36735-EN-1303212.6 CE conformityThis device fullls the legal requirements of the applicable EC guide-lines.
6010 SupplementVEGABAR 55 • Probus PA36735-EN-130321StainlesssteelhousinginprotectionratingIP66/IP68(1bar)117 mm (4.61")~ 103 mm(4.06&
6110 SupplementVEGABAR 55 • Probus PA36735-EN-13032112368 mm(2.68")68 mm(2.68")92 mm(3.62")42mm(1.65")40mm(1.57")110 mm x 90
6210 SupplementVEGABAR 55 • Probus PA36735-EN-130321VEGABAR55,threadedttingGG GL - 180°CGNGG - 180°C/200°CBA / BB BE78 mm(3 5/64")118 mm(4 4
6310 SupplementVEGABAR 55 • Probus PA36735-EN-130321VEGABAR55,hygienictting178 mm(3 5/64")78 mm(3 5/64")ø 64 mm(2 33/64")78 mm(3
6410 SupplementVEGABAR 55 • Probus PA36735-EN-130321VEGABAR55,hygienictting278 mm(3 5/64")78 mm(3 5/64")78 mm(3 5/64")78 mm(3 5/6
6510 SupplementVEGABAR 55 • Probus PA36735-EN-130321VEGABAR55,angeconnection3 15/32"4 1/64"5 7/16" 1/8" 1/8" 1/8"4x
6610 SupplementVEGABAR 55 • Probus PA36735-EN-13032110.4 Industrial property rightsVEGA product lines are global protected by industrial property ri
67INDEXVEGABAR 55 • Probus PA36735-EN-130321INDEXAAccessories – Display and adjustment module 10 – External display and adjustment unit 11 – Flange
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36735-EN-130321All statements concerning scope of delivery, application, practi
73 Product descriptionVEGABAR 55 • Probus PA36735-EN-1303213 Product description3.1 CongurationThe scope of delivery encompasses:• VEGABAR 55 pres
83 Product descriptionVEGABAR 55 • Probus PA36735-EN-130321213Fig. 1: Example of a VEGABAR 55 with process tting G1½ A and plastic hous-ing1 Housin
93 Product descriptionVEGABAR 55 • Probus PA36735-EN-130321This operating instructions manual applies to the following instrument versions:• Software
Kommentare zu diesen Handbüchern