Vega VEGABAR 63 Foundation Fieldbus Bedienungsanleitung Seite 53

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 76
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 52
- Connec
tion between IP 68 transmitter
and external electronics housing
PUR, FEP, PE
- Type plate support with IP 68 version on
cable
PE hard
Weight approx. 0.8 kg (1.764 lbs)
Output variable
Output
- Signal digital output signal, Foundation Fieldbus protocol
- Physical layer according to IEC 61158-2
Channel Numbers
- Channel 1 Primary Value
- Channel 2 Secondary Value 1
- Channel 3 Secondary Value 2
- Channel 4 Temperature Value
Transmission rate 31.25 Kbit/s
Current value 10 mA, ±0.5 mA
Dynamic behaviour output
Run-up time approx. 10 s
90 %
100 %
10 %
t
t
T
A
t
t
S
2
1
Fig. 28: Sudden
change of the process variable, dead time t
T
, rise time t
A
and step response time t
S
1 Process variable
2 Output signal
Dead time 150 ms
Rise time 100 ms (10 90 %)
Step response time 250 ms (ti: 0 s, 10 90 %)
Damping (63 % of the input variable) 0 999 s, adjustable