Caution:
No greas
e should be used when screwing the NPT cable gland or
steel tube into the threaded insert. Standard grease can contain
additives that corrode the connection between threaded insert and
housing. This would inuence the stability of the connection and the
tightness of the housing.
If screened cable is necessary, connect the cable screen on both ends
to ground potential. In the sensor, the screen must be connected
directly to the internal ground terminal. The ground terminal on the
outside of the housing must be connected to the potential equalisation
(low impedance).
If potential equalisation currents are expected, the connection on the
processing side must be made via a ceramic capacitor (e. g. 1 nF,
1500 V). The low frequency potential equalisation currents are thus
suppressed, but the protective eect against high frequency interfer-
ence signals remains.
Take note of the corresponding installation regulations for Ex
appl
ications. In particular, make sure that no potential equalisation
currents ow over the cable screen. In case of grounding on both sides
this can be achieved by the use of a capacitor or a separate potential
equalisation.
5.2 Connection procedure
Proceed as follows:
1 Unscrew the housing cover
2 If an indicating and adjustment module is installed, remove it by
turning it slightly to the left.
3 Loosen compression nut of the cable entry
4 Remove approx. 10 cm of the cable mantle, strip approx. 1 cm
insulation from the individual wires
5 Insert the cable through the cable gland into the sensor
6 Lift the opening levers of the terminals with a screwdriver (see
following illustration)
7 Insert the wire ends into the open terminals according to the wiring
plan
8 Press down the opening levers of the terminals, you will hear the
terminal spring closing
9 Check the hold of the wires in the terminals by lightly pulling on
them
10 Connect the screen to the internal ground terminal, connect the
outer ground terminal with potential equalisation
Cable screening and
grounding
Select connec-
tion cable for Ex
applications
Single/Double chamber
housing