10 Supplement
VEGABAR 66 • 4 … 20 mA/HART - climate compensated
36738-EN-130321
Thespecicationsareonlyanoverviewandrefertothemeasuringcell.Limitationsduetothema-
terialandversionoftheprocessttingarepossible.Thespecicationsonthenameplateapply.
Nominalrange Overload capacity, max.
pressure
Overload capacity, min. pres-
sure
Gauge pressure
0 … +3 psig +500 psig -15 psig
0 … +6 psig +700 psig -15 psig
0 … +15 psig +700 psig -15 psig
0 … +35 psig +950 psig -15 psig
0 … +70 psig +950 psig -15 psig
0 … +150 psig +1300 psig -15 psig
0 … +350 psig +1900 psig -15 psig
0 … +900 psig +2900 psig -15 psig
Referenceconditionsandactuatingvariables(accordingtoDINEN60770-1)
Reference conditions according to DIN EN 61298-1
Ʋ Temperature +15 … +25 °C (+59 … +77 °F)
Ʋ Relative humidity 45 … 75 %
Ʋ Air pressure 860 … 1060 mbar/86 … 106 kPa (12.5 … 15.4 psig)
Determination of characteristics Limit point adjustment according to IEC 61298-2
Characterstic curve Linear
Reference installation position upright, diaphragm points downward
Inuenceoftheinstallationposition < 0.2 mbar/20 Pa (0.003 psig)
Deviation determined according to the limit point method according to IEC 60770
12)
Applies to the digitalsignaloutput(HART,ProbusPA,FoundationFieldbus)aswellastoana-
logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
Deviation
Ʋ Turn down 1 : 1 up to 5 : 1 < 0.1 %
Ʋ Turn down > 5 : 1 < 0.02 % x TD
Inuenceoftheproductorambienttemperature
Averagetemperaturecoecientofthezerosignalandtheoutputspan
Applies to the digitalsignaloutput(HART,ProbusPA,FoundationFieldbus)aswellastoana-
logue current output 4 … 20 mA and refers to the set span. Turn down (TD) is the ratio nominal
measuring range/set span.
12)
Incl. non-linearity, hysteresis and non-repeatability.