68
10 Appendice
VEGABAR 81 • Protocollo Modbus e LevelMaster
46293-IT-131205
Register Name Register Number Type Note
SV 2104 DWord SecondaryVariableinByteOrderDCBA(LittleEn-
dian)
TV 2106 DWord ThirdVariableinByteOrderABCDDCBA(LittleEn-
dian)
QV 2108 DWord QuarternaryVariableinByteOrderDCBA(LittleEn-
dian)
Status 2200 DWord See Register 100
PV 2202 DWord PrimaryVariableinByteOrderBACD(MiddleEndian)
SV 2204 DWord SecondaryVariableinByteOrderBACD(MiddleEn-
dian)
TV 2206 DWord ThirdVariableinByteOrderBACD(MiddleEndian)
QV 2208 DWord QuarternaryVariableinByteOrderBACD(MiddleEn-
dian)
Unit Codes for Register 104, 108, 112, 116
Unit Code Measurement Unit
32 Degree Celsius
33 Degree Fahrenheit
40 US Gallon
41 Liters
42 Imperial Gallons
43 Cubic Meters
44 Feet
45 Meters
46 Barrels
47 Inches
48 Centimeters
49 Millimeters
111 Cubic Yards
112 Cubic Feet
113 Cubic Inches
10.4 Comandi RTU Modbus
FC3 Read Holding Register
Tramite questo comando è possibile leggere un numero qualsiasi (1-127) di holding register. Vengo-
notrasmessiilregistroiniziale,apartiredalqualevaeettutalalettura,eilnumerodiregistri.