9 Diagnosis, Asset Management and service
VEGAPULS 66 • Foundation Fieldbus
36522-EN-121011
The following table shows the error codes and text messages in the
status message "Maintenance" and provides information on causes
as well as corrective measures.
Code
Text mes-
sage
Cause Rectication
M500
Error with the
reset delivery
status
With the reset to delivery
status, the data could not
be restored
Repeat reset
Load XML le with sensor
data into the sensor
M501
Error in the
non-active
linearization
table
Hardware error EEPROM Exchanging the electronics
Send instrument for repair
M502
Error in the
diagnosis
memory
Hardware error EEPROM Exchanging the electronics
Send instrument for repair
M503
Reliability too
low
The echot/noise ratio is the
small for a reliable meas-
urement
Check installation and
process conditions
Clean the antenna
Change polarisation direc-
tion
Use instrument with higher
sensitivity
M504
Error on an
device inter-
face
Hardware defect Check connections
Exchanging the electronics
Send instrument for repair
M505
No echo avail-
able
Level echo can no longer
be detected
Clean the antenna
Use a more suitable
antenna/sensor
Remove possible false
echoes
Optimize sensor position
and orientation
9.4 Rectify faults
The operator of the system is responsible for taking suitable meas-
ures to rectify faults.
The rst measures are:
Evaluation of fault messages, for example via the indicating and
adjustment module
Checking the output signal with 4 … 20 mA instruments
Treatment of measurement errors
Further comprehensive diagnostics options oer a PC with the soft-
ware PACTware and the suitable DTM. In many cases, the reasons
can be determined in this way and faults can be rectied.
Maintenance
Reaction when malfunc-
tions occur
Procedure for fault recti-
cation
Seitenansicht 51