Operating InstructionsRadar sensor for continuous level measurement of liquidsVEGAPULS 66Foundation FieldbusDocument ID: 36522
103 Product descriptionVEGAPULS 66 • Foundation Fieldbus36522-EN-1210113 Product description3.1 CongurationThe type label contains the most importa
113 Product descriptionVEGAPULS 66 • Foundation Fieldbus36522-EN-121011The instrument is available in two dierent electronics versions. Each version
123 Product descriptionVEGAPULS 66 • Foundation Fieldbus36522-EN-1210113.3 Packaging, transport and storageYour instrument was protected by packaging
133 Product descriptionVEGAPULS 66 • Foundation Fieldbus36522-EN-121011It is suitable for measured value indication and adjustment of plics® sensors a
144 MountingVEGAPULS 66 • Foundation Fieldbus36522-EN-1210114 Mounting4.1 General instructionsWith instruments with threaded process tting, suitable
154 MountingVEGAPULS 66 • Foundation Fieldbus36522-EN-121011center of dished or round vessel tops, multiple echoes can arise. These can, however, be s
164 MountingVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Fig.8:MountingoftheradarsensorwithinowingmediumThe socket piece should be dimens
174 MountingVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Tip:VEGAPULS 66 is optionally also available with antenna extension. The antenna length ca
184 MountingVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Fig. 13: AgitatorsThrough the action of lling, stirring and other processes in the vessel
194 MountingVEGAPULS 66 • Foundation Fieldbus36522-EN-1210110%100%455678101238Fig.14:Congurationsurgepipe1 Radar sensor2 Marking of the polaris
2Quick startVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Quick startThe quick start enables a quick setup with many applications. You can nd furth
204 MountingVEGAPULS 66 • Foundation Fieldbus36522-EN-121011• The tube diameter must be at least DN 40 or 1½" with antenna size 40 mm (1½")•
214 MountingVEGAPULS 66 • Foundation Fieldbus36522-EN-1210110 %100 %125436Fig.15:Congurationbypass1 Radar sensor2 Marking of the polarisation di
224 MountingVEGAPULS 66 • Foundation Fieldbus36522-EN-121011• For the parameter adjustment, select "Application standpipe" and enter the tub
235 Connecting to the bus systemVEGAPULS 66 • Foundation Fieldbus36522-EN-1210115 Connecting to the bus system5.1 Preparing the connectionAlways kee
245 Connecting to the bus systemVEGAPULS 66 • Foundation Fieldbus36522-EN-1210115.2 ConnectingThe voltage supply and signal output are connected via t
255 Connecting to the bus systemVEGAPULS 66 • Foundation Fieldbus36522-EN-1210118. Connect the screen to the internal ground terminal, connect the ou
265 Connecting to the bus systemVEGAPULS 66 • Foundation Fieldbus36522-EN-121011+Bus2312( )(-)1Fig. 20: Connection compartment, double chamber housin
275 Connecting to the bus systemVEGAPULS 66 • Foundation Fieldbus36522-EN-121011+Bus212( )(-)1Fig. 23: Connection compartment, double chamber housing
285 Connecting to the bus systemVEGAPULS 66 • Foundation Fieldbus36522-EN-121011• Internal check of the electronics• Indication of the instrument type
296 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-1210116 Set up with the indicating and adjustment modul
3Quick startVEGAPULS 66 • Foundation Fieldbus36522-EN-1210113. Select in the menu item "Application" the vessel, the application and the ve
306 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-1210111 2Fig. 27: Insertion of the indicating and adjust
316 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011 – Edit parameter – Save value• [->] key: – Pre
326 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011SetupEach medium has dierent reection properties
336 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011The following features form the basis of the appli
346 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Standpipe:• Product speed: very fast lling and em
356 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011• Process/measurement conditions: – Ice and conden
366 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011 – Large distance to the medium – Large angles of
376 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Enter the requested parameters via the appropriate
386 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011100%0%1,5 m(59.1")15 m(590.6")21Fig. 29:
396 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-1210114. Enter the suitable distance value in m for the
4ContentsVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Contents1 About this document1.1 Function ...
406 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011The "Echo curve" shows the signal streng
416 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011• Vessel installations such as struts• Agitators•
426 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011The menu item "Delete" is used to comple
436 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011• Setup: Resetting of the parameter settings to th
446 Set up with the indicating and adjustment moduleVEGAPULS 66 • Foundation Fieldbus36522-EN-121011If the instrument is equipped with an indicating a
457 Setup with PACTwareVEGAPULS 66 • Foundation Fieldbus36522-EN-1210117 Setup with PACTware7.1 Connect the PC312Fig. 30: Connection of the PC direc
467 Setup with PACTwareVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Fig. 31: Example of a DTM viewAll device DTMs are available as a free-of-charge
478 Set up with other systemsVEGAPULS 66 • Foundation Fieldbus36522-EN-1210118 Set up with other systems8.1 DD adjustment programsDevice description
489 Diagnosis, Asset Management and serviceVEGAPULS 66 • Foundation Fieldbus36522-EN-1210119 Diagnosis, Asset Management and service9.1 MaintenanceIf
499 Diagnosis, Asset Management and serviceVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Further echo curves: Up to 10 echo curves can be stored in
5ContentsVEGAPULS 66 • Foundation Fieldbus36522-EN-1210119.3 Asset Management function ... 499.4 Rectify f
509 Diagnosis, Asset Management and serviceVEGAPULS 66 • Foundation Fieldbus36522-EN-121011The following table shows the codes and text messages of th
519 Diagnosis, Asset Management and serviceVEGAPULS 66 • Foundation Fieldbus36522-EN-121011CodeText mes-sageCause Rectication PA DevS-pecDiagnosisF26
529 Diagnosis, Asset Management and serviceVEGAPULS 66 • Foundation Fieldbus36522-EN-121011The following table shows the error codes and text messages
539 Diagnosis, Asset Management and serviceVEGAPULS 66 • Foundation Fieldbus36522-EN-121011The below tables show typical examples of application-relat
549 Diagnosis, Asset Management and serviceVEGAPULS 66 • Foundation Fieldbus36522-EN-1210119.4 MeasurementerrorduringllingFault description Error
559 Diagnosis, Asset Management and serviceVEGAPULS 66 • Foundation Fieldbus36522-EN-1210119.4 Measurement error during emptyingFault description Err
569 Diagnosis, Asset Management and serviceVEGAPULS 66 • Foundation Fieldbus36522-EN-121011In both cases, the serial number of the sensor is needed. T
5710 DismountingVEGAPULS 66 • Foundation Fieldbus36522-EN-12101110 Dismounting10.1 Dismounting stepsWarning:Before dismounting, be aware of dangerous
5811 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-12101111 Supplement11.1 Technical dataGeneral data316L corresponds to 1.4404 or 1.4435Materi
5911 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-1210113421Fig. 47: Data of the input variable1 Reference plane2 Measured variable, max. mea
61 About this documentVEGAPULS 66 • Foundation Fieldbus36522-EN-1210111 About this document1.1 FunctionThis operating instructions manual provides al
6011 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Installation reference conditions Ʋ Min. distance to installations > 200 mm (7.874 i
6111 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Gas phase Temperature Pressure1 bar (14.5 psig)10 bar (145 psig)50 bar (725 psig)100 ba
6211 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Seal Antenna impedance coneProcess temperature (measured on the process tting)FFKM (Ka
6311 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011 Ʋ Cable gland M20 x 1.5 (cable: ø 5 … 9 mm) Ʋ Cable entry ½ NPT Ʋ Blind stopper M20 x
6411 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Integrated clockDate format Day.Month.YearTime format 12 h/24 hTime zone Ex factory CET
6511 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Revisions Data DD-Revision Rev_01CFF-File 010101.cDevice Revision 0101.o0101.symC-Re
6611 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011carries out the min./max. adjustment (Secondary Value 1), carries out a linearization (
6711 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011ent time constants with the primary and secondary process measurement.Fig. 52: Schemati
6811 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Fig. 54: Schematic presentation function block Signal CharacterizerFunction block Integ
6911 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Fig. 55: Schematic presentation function block IntegratorFunction block Input SelectorT
72 For your safetyVEGAPULS 66 • Foundation Fieldbus36522-EN-1210112 For your safety2.1 Authorised personnelAll operations described in this operatin
7011 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011The following algorithms are available:• Flow compensation, linear• Flow compensation,
7111 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011FF desciptor Description UnitSECONDARY_VALUE_1_TYPESecondary value 1 typeSECONDARY_VALU
7211 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011FF desciptor Description UnitFALSE_SIGNAL_CMD_CON-FIGURATION2Gradient of the manual sec
7311 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011FF desciptor Description UnitECHO_CURVE_PLICSCOM_LIMITSParameters as start and endAPPRO
7411 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Aluminium housing21ø 86 mm (3.39")~ 116 mm (4.57")116 mm (4.57")M20x1,5M
7511 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011Stainless steel housing~ 69 mm(2.72")ø 79 mm(3.11")117 mm (4.61")M20x1,5
7611 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011VEGAPULS 66, standard versiony60 mm(2.36")yDN 50 PN 40-DN 80 PN 4068DN 100 PN 1611
7711 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011tube diameters 10 mmVEGAPULS 66, version with horn antenna83 mm(3.27")16 mm(0.63&q
7811 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-121011VEGAPULS 66, high temperature versions200 mm (7.87")337 mm (13.27")21Fig. 66:
7911 SupplementVEGAPULS 66 • Foundation Fieldbus36522-EN-12101111.4 Industrial property rightsVEGA product lines are global protected by industrial p
82 For your safetyVEGAPULS 66 • Foundation Fieldbus36522-EN-1210112.5 CE conformityThe device fullls the legal requirements of the applicable EC gui
80INDEXVEGAPULS 66 • Foundation Fieldbus36522-EN-121011INDEXAAccessories – External indicating and adjustment unit 12 – External radio unit 13 – Fla
81NotesVEGAPULS 66 • Foundation Fieldbus36522-EN-121011
82NotesVEGAPULS 66 • Foundation Fieldbus36522-EN-121011
83NotesVEGAPULS 66 • Foundation Fieldbus36522-EN-121011
Printing date:VEGA Grieshaber KGAm Hohenstein 11377761 SchiltachGermany36522-EN-121011All statements concerning scope of delivery, application, practi
92 For your safetyVEGAPULS 66 • Foundation Fieldbus36522-EN-1210112.9 Environmental instructionsProtection of the environment is one of our most impo