9 Diagnosis, Asset Management and service
VEGAPULS 66 standpipe version • Modbus and Levelmaster protocol
41367-EN-121011
The below tables show typical examples of application-relevant meas-
urement errors with standpipe versions. The measurement errors are
dierentiated according to:
Constant level
Filling
Emptying
The images in column "Errorpattern" show the real level with a bro-
ken line and the level displayed by the sensor as a continuous line.
1
2
Level
time
0
Fig.16:Thebrokenline1showsthereallevel,thecontinuousline2showsthe
level displayed by the sensor
Instructions:
Wherever the sensor displays a constant value, the reason could
also be the fault setting of the current output to "Hold value"
In case of a too low level indication, the reason could be a line
resistance that is too high
9.4 Measurement error with constant level
Fault description Error pattern Cause Rectication
1. Measured value
shows a too low or too
high level
Level
time
0
Min./max. adjustment not
correct
Adapt min./max. adjustment
Wrong linearization curve Adapt linearization curve
Installation in a bypass tube or
standpipe, hence running time
error (small measurement error
close to 100 %/large error close
to 0 %)
Check parameter "Application"
with respect to vessel form,
adapt if necessary (bypass,
standpipe, diameter)
2. Measured value
jumps towards 100 %
Level
time
0
Due to the process, the ampli-
tude of the product echo sinks
A false signal suppression was
not carried out
Carry out false signal suppres-
sion
Amplitude or position of a
false echo has changed (e.g.
condensation, buildup); false
signal suppression no longer
matches
Determine the reason for the
changed false echo, carry out
false signal suppression, e.g.
with condensation
Treatment of measure-
ment errors with stand-
pipe versions