9 Diagnosis, Asset Management and service
VEGAPULS 66 standpipe version • Modbus and Levelmaster protocol
41367-EN-121011
9.4 Measurementerrorduringlling
Fault description Error pattern Cause Rectication
3. Measured value re-
mains in the area of the
bottom during lling
Level
time
0
Echo from the tank bottom
larger than the product echo,
for example, with products with
ε
r
< 2.5 oil-based, solvents
Check application parameters
Medium, Vessel height and
Floor form, adapt if necessary
4. Measured value
jumps to ≥ 100 % or
0 m distance
Level
time
0
Level echo is no longer
detected in the close range
due to foam generation or false
echoes in the close range. The
sensor goes into overll protec-
tion mode. The max. level (0 m
distance) as well as the status
message "Overll protection"
are outputted.
Check measuring site: Antenna
must protrude out of the socket
Remove contamination on the
antenna
Use a sensor with a more suit-
able antenna
9.4 Measurement error during emptying
Fault description Error pattern Cause Rectication
5. Measured value re-
mains unchanged in
the close range during
emptying
Level
time
0
False echo larger than the level
echo
Level echo too small
Remove false echoes in the
close range. Check: Antenna
must protrude out of the socket
Remove contamination on the
antenna
Minimize interfering instal-
lations in the close range by
changing the polarization
direction
After removing the false ech-
oes, the false signal suppres-
sion must be deleted. Carry out
a new false signal suppression
6. Measured value
jumps towards 0 %
during emptying
Level
time
0
Echo from the tank bottom
larger than the product echo,
for example, with products with
ε
r
< 2.5 oil-based, solvents
Check application parameters
Medium type, Vessel height and
Floor form, adapt if necessary
Depending on the reason for the fault and the measures taken, the
steps described in chapter "Setup" must be carried out again or must
be checked for plausibility and completeness.
Should these measures not be successful, please call in urgent cases
the VEGA service hotline under the phone no. +49 1805 858550.
The hotline is also available outside the normal working hours on
seven days a week around the clock.
Since we oer this service worldwide, the support is in the English
language. The service itself is free of charge, the only costs involved
are the normal call charges.
9.5 Exchanging the electronics module
If the electronics module is defective, it can be replaced by the user.
Reaction after fault recti-
cation