8Maintenanceandfaultrectication
PLICSRADIO R61 • Wireless receiving unit (single channel)
32625-EN-130228
Error code Cause Rectication
E035 ROM CRC error – Switchtheinstrumentoandon
– Carry out a reset
– Send instrument for repair
E036 Instrument software
not executable (dur-
ing software update
or after failed update)
– Waituntilsoftwareupdateisnished
– Carry out another software update
E042 Hardware error with
selfcheck
– Send instrument for repair
E053 Sensor measuring
range not read cor-
rectly
– Communication error: Check sensor
cable and screening
E086 Error communication
hardware (initiali-
sation of the radio
module failed)
– Initialisation is carried out automati-
cally. If the error exists permanently,
send instrument for repair
Depending on the reason for the fault and the measures taken, the
steps described in chapter "Set up" may have to be carried out again.
8.3 Instrument repair
If a repair is necessary, please proceed as follows:
You can download a return form (23 KB) from our Internet homepage
www.vega.com under: "Downloads - Forms and certicates - Repair
form".
By doing this you help us carry out the repair quickly and without hav-
ing to call back for needed information.
•
Printandlloutoneformperinstrument
•
Clean the instrument and pack it damage-proof
•
Attach the completed form and, if need be, also a safety data
sheet outside on the packaging
•
Please ask the agency serving you for the address of your return
shipment.Yo u canndtherespectivecontactdataonourwebsite
www.vega.com under: "Company - VEGA worldwide"
Reactionafterfaultrecti-
cation