Vega SOLITRAC 31 4 … 20 mA_HART - four-wire With SIL qu Bedienungsanleitung Seite 34

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 84
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 33
34
7 Set up with the display and adjustment module
SOLITRAC 31 • 4 … 20 mA/HART - four-wire
43387-EN-131119
Enter in the menu window "Max. process value" the max. level (full),
for example in "m". This corresponds to an output current of 20 mA.
Enter in the menu window "Min. process value" the min. level (empty),
for example in "m". This corresponds to an output current of 4 mA.
In this menu item you can carry out the adjustment of the sensor.
Caution:
Duringtherstsetuporafteraninstrumentreset,thelinearisation
stands at the preset value pair (90000 ct/s 0 % and 0 ct/s 100 %).
These values are not suitable for your application and must be re-
placed by real values. Delete this value pair in the following procedure
and carry out the linearisation.
Due to the measuring principle, there is no linear relationship between
pulse rate and level. Hence, this adjustment (i.e. linearisation) must in
any case be carried out.
If you have a non-linear vessel (e.g. spherical tank), you have to carry
out this adjustment with as many points as possible.
Note:
Ifyoucannotllthevesselwiththeoriginalmedium,itisalsopossible
to carry out the adjustment with water.
Prerequisites:
Radiation is switched on - Source container is set to "ON"
Thevesseliseithercompletelylled(100%)orcompletelyemptied
(0 %).
Dependingonthefactifthevesselislledoremptied,youcancar-
riedoutrstthefullortheemptyadjustment.TheSOLITRAC31sorts
the points automatically according to their level.
Select "Show table" to display and edit the linearization points.
Setup/Linearisation
Seitenansicht 33
1 2 ... 29 30 31 32 33 34 35 36 37 38 39 ... 83 84

Kommentare zu diesen Handbüchern

Keine Kommentare