7 Set up with the display and adjustment module
SOLITRAC 31 • 4 … 20 mA/HART - four-wire
43387-EN-131119
Information:
Inthisoperatinginstructionsmanual,theinstrument-specicparam-
eters are described. Further general parameters are described in the
operating instructions manual "Display and adjustment module".
Caution:
Duringtherstsetuporafteraninstrumentresettheinstrumentstarts
with preset standard values. These value are not suitable for your ap-
plication and must be replaced by real values.
Carry out a setup in the sequence described in the following.
With this menu item you safeguard the sensor parameters against
unauthorizedorunintentionalmodications.
To avoid possible errors during parameterization in a non-safe user
environment,avericationprocedureisusedthatmakesitpossible
to detect parameterization errors reliably. For this, safety-relevant
parametersmustbeveriedbeforetheyarestoredinthedevice.In
normal operating condition, the instrument is also locked against
parameter changes through unauthorized access.
For this reason, the instrument is shipped in locked conditon. The PIN
in the delivery status is "0000".
Afterachange,allsafety-relevantparametersmustbeveried.For
this purpose, a character string comparison must be carried out. This
is used to check the character respresentation and the communica-
tion channels.
Conrmifthetwocharacterstringsareidentical.Thevericationtexts
are provided in German and with all other menu languages in English.
Inasecondstep,allmodiedsafety-relevantparametersarelisted.
Conrmthemodiedvalues.
If the described process of parameter adjustment was run through
completely and correctly, the instrument will be locked and hence
ready for operation.
Instrument start
Lock setup - adjustment