9 Diagnosis, asset management and service
VEGABAR 81 • 4 … 20 mA/HART
45018-EN-131010
Code
Text mes-
sage
Cause Rectication
F013
no measured
value avail-
able
No valid measured value
available
Gauge pressure or low
pressure, measuring cell
defective
F017
Adjustment
span too small
Adjustment not within
specication
Change the adjustment
according to the limit values
F025
Error in the
linearization
table
Index markers are not con-
tinuously rising, for examle
unlogical value pairs
Checklinearizationtable
Delete table/Create new
F036
no operable
sensor soft-
ware
Failed or interrupted soft-
ware update
Repeat software update
Check electronics version
Exchanging the electronics
Send instrument for repair
F040
Error in the
electronics
Hardware defect Exchanging the electronics
Send instrument for repair
F041
Error in the
electronics
No connection to the sensor
electronics
Check connection to the
sensor electronics (with
detachable version)
F080 General software error Separate operating voltage
briey
F113
Communi-
cation error,
display and
adjustment
module
Adjustment
software
PACTware out
of order
EMC interference RemoveEMCinuences
F125
Unpermissi-
ble electronics
temperature
Temperature of the elec-
tronicsinthenon-specied
section
Check ambient temperature
Isolate electronics
Use instrument with higher
temperature range
F260
Error in the
calibration
Error in the calibration car-
ried out in the factory
Error in the EEPROM
Exchanging the electronics
Send instrument for repair
F261
Error in the
conguration
Error during setup
Error when carrying out a
reset
Repeat setup
Repeat reset