28
6 Set up with the display and adjustment module
VEGABAR 81 • HART and accumulator pack
45026-EN-131107
If these values are not known, an adjustment with levels of for exam-
ple 10 % and 90 % is also possible. By means of these settings, the
realllingheightisthencalculated.
The real product level during this adjustment is not important, be-
cause the min./max. adjustment is always carried out without chang-
ing the product level. These settings can be made ahead of time
without the instrument having to be installed.
Note:
If the adjustment ranges are exceeded, the entered value will not be
accepted. Editing can be interrupted with [ESC] or corrected to a
value within the adjustment ranges.
Fortheotherprocessvariablessuchase.g.processpressure,dier-
entialpressureorow,theadjustmentisperformedinlikemanner.
Proceed as follows:
1. Select the menu item "Setup" with [->]andconrmwith[OK].
Now select with [->] the menu item "zero adjustment"andconrm
with [OK].
2. Edit the mbar value with [OK] and set the cursor to the requested
position with [->].
3. Set the requested mbar value with [+] and store with [OK].
4. Move with [ESC] and [->] to the span adjustment
Thezeroadjustmentisnished.
Information:
Thezeroadjustmentshiftsthevalueofthespanadjustment.The
span,i.e.thedierencebetweenthesevalues,however,remains
unchanged.
For an adjustment with pressure, simply enter the actual measured
value indicated at the bottom of the display.
If the adjustment ranges are exceeded, the message "Outside param-
eter limits" appears. The editing procedure can be aborted with [ESC]
or the displayed limit value can be accepted with [OK].
Proceed as follows:
1. Select with [->]themenuitem"Spanadjustment"andconrm
with [OK].
Setup - zero adjustment
Setup - span adjustment