6 Set up with the display and adjustment module
VEGABAR 81 • HART and accumulator pack
45026-EN-131107
Basic settings: Resetting the parameter settings incl. special
parameters to the default values of the respective instrument. A pro-
grammedlinearizationcurveaswellasthemeasuredvaluememory
is deleted.
The following table shows the default values of the instrument. De-
pending on the instrument version or application, all menu items may
notbeavailableorsomemaybedierentlyassigned:
Reset - Setup
Menu item Parameter Default value
Measurement
loop name
Sensor
Application Application pro-
cess pressure
Application level
No reset
Slave for elec-
tronicdierential
pressure
No reset
Units Unit of measure-
ment
mbar (with nominal measuring range
≤400mbar)
bar (with nominal measuring rang-
es≥1bar)
Temperature unit °C
Position correc-
tion
0.00 bar
Adjustment Zero/Min. adjust-
ment
0.00 bar
0.00 %
Span/Max. adjust-
ment
Nominal measuring range in bar
100.00 %
Damping Integration time 0.0 s
Current output Current output -
Mode
Output characteristics
4 … 20 mA
Reaction when malfunction occurs
≤3.6mA
Current output -
Min./Max.
3.8 mA
20.5 mA
Lock adjustment Released
Reset - Display
Menu item Default value
Menu language Order-specic
Displayed value 1 Current output in %
Displayed value 2 Measuring cell temperature in °C
Backlight Switchedo