Vega FIELDBARRIER Bedienungsanleitung Seite 9

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 36
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 8
FieldBarrier
Subject to reasonable modifications due to technical advances. Copyright Pepperl+Fuchs, Printed in Germany
Pepperl+Fuchs Group • Tel.: Germany +49 621 776-0 • USA +1 330 4253555 • Singapore +65 67799091 • Internet http://www.pepperl-fuchs.com
08/2007 122329
7
4.2 Marking
FieldBarriers are identified by:
4.3 Ambient conditions
For the ambient temperature range, please refer to the respective data sheet.
4.4 Mounting and dismounting
Commissioning and installation must only be performed by specialist who are trained
specifically for this purpose.
Recognized rules of the technology and setup requirements must be maintained dur-
ing mounting and dismounting. Especially for tasks on electrical systems, special
safety requirements must be observed. Special attention must be paid to the following
points:
1. Has the FieldBarrier been installed in accordance with specifications?
2. Is the FieldBarrier free of damage?
4.4.1 Mounting and dismounting the F2D0-FB-Ex4.***
The housing of FieldBarrier F2D0-FB-Ex4.*** is designed in protection class IP 67. It
is intended for panel mounting. 2 screws with a diameter of 6 mm should be used for
mounting.
The mounting material should be selected according to the nature of the sub-surface
(the wall). When selecting mounting material, care must be taken that it will ensure a
secure fastening. The torque to be used for the mounting screws depends on the
screws being used.
Type F*D0-FB-Ex4.CG should be mounted so that the cable glands are protected
from the effects of mechanical hazards.
The cover screws of the FieldBarrier should be tightened with a torque of 2.5 Nm.
4.4.2 Mounting/dismounting of RD0-FB-Ex4
FieldBarrier RD0-FB-Ex4 is designed for mounting on a 35-mm DIN rail in accordance
with EN 50 022. It must be mounted in a housing that corresponds to at least protec-
tion class IP 54. The housing must also have an EC declaration of conformity in ac-
cordance with EC 94/9.
FieldBarrier F2D0-... FieldBarrier RD0-...
Pepperl + Fuchs Pepperl + Fuchs
D-68307 Mannheim D-68307 Mannheim
F2D0-FB-Ex*.*** RD0-FB-Ex*.***
PTB 02 ATEX 2086 PTB 02 ATEX 2086
¬ II 2 (1 G/D) G Ex me [ia] IIC T4 ¬ II 2 (1 G/D) G Ex me [ia] IIC T4
¬ Ex tD A22 IP54 T135 °C
(non-conductive dust)