6 Set up with the display and adjustment module PLICSCOM
VEGABAR 55 • 4 … 20 mA
36733-EN-130321
Iftheadjustmentrangesareexceeded,themessage"Outside param-
eter limits"appears.Theeditingprocedurecanbeabortedwith[ESC]
or the displayed limit value can be accepted with [OK].
Proceed as follows:
1. Editthe%valueinthemenuitem"Max. adjustment"with[OK].
Max. adjustment
+100.0 %
=
+1000.0 mbar
0000.0 mbar
Information:
The displayed pressure for 100 % corresponds to the nominal meas-
uring range of the sensor (in the above example 1 bar = 1000 mbar).
2. Set the requested percentage value with [->] and [OK].
3. Conrmwith[OK] and edit the requested mbar value.
4. Set the requested mbar value with [+] and [->].
5. Conrmwith[OK] and move to the menu overview with [ESC].
Themax.adjustmentisnished.
Information:
Foranadjustmentwithlling,simplyentertheactualmeasuredvalue
indicated at the bottom of the display.
Iftheadjustmentrangesareexceeded,themessage"Outside param-
eter limits"appears.Theeditingprocedurecanbeabortedwith[ESC]
or the displayed limit value can be accepted with [OK].
Process pressure measurement
Set up VEGABAR 55 in the following sequence:
1. Selectapplication"Processpressuremeasurement"
2. Select the unit of measurement
3. Carry out a position correction
4. Carryingoutzeroadjustment
5. Carry out span adjustment
Inthemenuitem"Adjustment unit"youselectthephysicalunitin
which the adjustment should be carried out, e.g. mbar, bar, psi…
Thepositioncorrectioncompensatestheinuenceofthemounting
positionorstaticpressureonthemeasurement.Itdoesnotinuence
the adjustment values.
Inthemenuitems"zero"and"span"youdeterminethespanofthe
sensor, the span corresponds to the end value.
Information:
The steps 1, 3 and 4 are not necessary for instruments which are
alreadypresetaccordingtocustomerspecications!
Youcanndthedataonthetypelabelontheinstrumentorinthe
menuitemsofthezero/spanadjustment.
Carry out max. adjust-
ment
Parameter adjustment
"Process pressure meas-
urement"