- Holds
the maximum sensor value. Write access resets to current value. Unit
derives from 'Sensor_range.unit'
- Write access resets to current value
l min_peak_sensor_value
- Holds the
minimum sensor value. Write access resets to current value. Unit
derives from 'Sensor_range.unit'
- Write
access resets to current value
l CAL_POINT_HI
- Highest calibrated value. For
calibration of the high limit point you give the high
measurement value (pressure) to the sensor and transfer this point as HIGH to the
transmitter. Unit derives from 'Sensor_range.unit'
l CAL_POINT_LO
- Lowest calibrated value. For
calibration of the low limit point you give the low
measurement value (pressure) to the sensor and transfer this point as LOW to the
transmitter. Unit derives from 'Sensor_range.unit'
l CAL_MIN_SPAN
- Minimum
calibration span value allowed. Necessary
to ensure that when calibration is
done, the two calibrated points (high and low) are not too close together. Unit derives
from 'Sensor_range.unit'
l SCALE_IN
- Min/max-adjustment: Uppe
r
and lower calibrated points of the sensor. Unit derives
from 'Sensor_range.unit'
l trimmed_value
- Sensor value after the trim processing. Unit
derives from 'Sensor_range.unit'
l sensor_sn
- Sensor serial number
l temperature
- Process temperature. Selected
as input to AIFB by setting 'Channel' = 4 . Unit derives
from 'Temperature.unit'
l temperature_unit
- Unit code of 'Temperature', 'Max/Min_peak_temperature_value'
- °C, °F, K, °R
l max_peak_temperature_value
- Holds the
maximum process temperature. Write access resets to current value.
Unit derives from 'Temperature.unit'
- Write
access resets to current value
l min_peak_temperature_value
- Holds the
minimum process temperature. Write access resets to current value.
Unit derives from 'Temperature.unit'
- Write
access resets to current value