Vega VEGABAR 52 Profibus PA Bedienungsanleitung Seite 48

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 68
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 47
48
10 Supplement
VEGABAR 52 • Probus PA
36719-EN-130321
Ʋ External housing IP 65, IP 66/IP 68 (0.2 bar)
Overvoltage category III
Protection class II
Approvals
Instruments with approvals can have dierent technical data depending on the version.
For that reason the associated approval documents of these instruments have to be carefully
noted. They are part of the delivery or can be downloaded under www.vega.com via "VEGA Tools"
and "serial number search" as well as via "Downloads" and "Approvals".
10.2 InformationonProbusPA
Instrumentmasterle
The instrument master le (GSD) contains the characteristic data of the Probus PA instrument.
These data are, e.g. the permissible transmission rates as well as information on diagnostics values
and the format of the measured value outputted by the PA instrument.
A bitmap le is also provided for the Probus network planning tool. This le is installed automati-
cally when the GSD le is integrated. The bitmap le is used for symbolic indication of the PA instru-
ment in the conguration tool.
Ident number
Each Probus instrument gets an unambiguous ident number (ID number) from the Probus user
organisation (PNO). This ID number is also included in the name of the GSD le. For VEGABAR 52
the ID number is 0x076F(hex) and the GSD le BR__076F.GSD. As an option to this manufactur-
er-specic GSD le, PNO provides also a general so-called prole-specic GSD le. For VEGABAR
52 you have to use the general GSD le PA139701.GSD. If the general GSD le is used, the sensor
must be set to the prole-specic ident number via the DTM software. By default, the sensor oper-
ates with the manufacturer-specic ID number.
Note:
When using the prole-specic GSD le, the PA-OUT value as well as the temperature
value are transmitted to the PLC (see block diagram "Cyclical data trac").
Cyclicaldatatrac
The master class 1 (e.g. PLC) cyclically reads out measured values from the sensor during opera-
tion. The below block diagram below shows which data can be accessed by the PLC.
Seitenansicht 47
1 2 ... 43 44 45 46 47 48 49 50 51 52 53 ... 67 68

Kommentare zu diesen Handbüchern

Keine Kommentare