50
10 Supplement
VEGABAR 52 • Probus PA
36719-EN-130321
Examplesoftelegramconguration
In the following you will see how the modules can be combined and how the appendant data tel-
egram is structured.
Example 1 (standard setting) with pressure value, temperature value and additional cyclical value:
•
AI (PA-OUT)
•
Temperature
•
Additional Cyclic Value
Byte-No.
1234 567891011121314
15
Format
Value
IEEE-754-
Floating point value
PA-OUT
(FB1)
Status
Status
(FB1)
IEEE-754-
Floating point value
Temperature
(FB2)
IEEE-754-
Floating point value
Additional Cyclic
Value
Status
Status
(FB2)
Status
Status
Fig. 30: Telegram conguration example 1
Example 2 with pressure value and temperature value without additional cyclical value:
•
AI (PA-OUT)
•
Temperature
•
Free Place
Byte-No.
1234 5678910
Format
Value
IEEE-754-
Floating point value
PA-OUT
Status
Status
(FB1)
IEEE-754-
Floating point value
Temperature
(FB2)
Status
Status
(FB2)
Fig. 31: Telegram conguration example 2
Example 3 with pressure value and additional cyclical value without temperature value:
•
AI (PA-OUT)
•
Free Place
•
Additional Cyclic Value
1234 5 6789 10
Status
Status
Status
Status
(FB1)
IEEE-754-
Floating point value
PA-OUT
(FB1)
IEEE-754-
Floating point value
Additional Cyclic
Value
Format
Value
Fig. 32: Telegram conguration example 3
Data format of the output signal
Byte4
Byte3
Byte2
Byte1
Byte0
Status Value (IEEE-754)
Fig. 33: Data format of the output signal
The status byte corresponds to prole 3.0 "Probus PA Prole for Process Control Devices" coded.
The status "Measured value OK" is coded as 80 (hex) (Bit7 = 1, Bit6 … 0 = 0).
The measured value is transferred as a 32 bit oating point number in the IEEE-754 format.
Kommentare zu diesen Handbüchern